07-2024
REFERENCE STANDARDS 
EU CONFORMITY DECLARATION 
Vemer declares that the device complies with the Communitary Directive
2014/53/EU (RED) with reference to the following standards: 
• EN 60730-2-7 • ETSI EN 301 489-1 • ETSI EN 301 489-17 • ETSI EN 300 328
 The full text of the EU Conformity Declaration is available at www.vemer.it address.
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
e-mail: info@vemer.it  -  web site: www.vemer.it 
V3IS01177-010 
 Mod. micro BT 
Manuals 
download 
PDF
1   Relay terminals
2   Cover for battery replacement
3   Green LED: power supply/Bluetooth 
  connection status
4   Key: manual switching relay/reset 
5   Terminals for power supply
6   Red LED: relay status indication
2INSTRUMENT DESCRIPTION and DIMENSION 
1
6
5
1
User manual 
TIME/ASTRONOMICAL SWITCH WITH BLUETOOTH
 Read all instructions carefully   
Electronic digital switch for the management of electrical loads over time through the relay 
(channel) available on board. Allows time programming (periodicity: daily or weekly) or 
astronomical (from sunset to sunrise). The Bluetooth interface allows it to be coupled with 
smartphone or tablet thanks to the free app. The application allows complete management 
of the device, allowing you to program and make settings directly on your smartphone, and 
then transfer all the data to the time switch. The reverse procedure is also possible, i.e. to 
copy the programming of a time switch on your mobile device. The backup battery allows 
you to keep the settings even in case of black-out and can be replaced through the cover 
on the front of the device. micro BT is an electronic device that perform actions of 1B type, 
intended to operate in environments with overvoltage category III and pollution degree 2 
according to the EN 60730-1 standard.
 
     Code              Model             Description
     VE797200     micro BT           Daily/weekly/astronomical time switch with 1 relay                                          
                                                         and Bluetooth interface 
  
  SAFETY WARNINGS 
  During product installation and operation it is necessary to observe the following 
  instructions: 
  1)  The product must be installed by a qualified person, strictly in observance of the
  connection diagrams shown in this manual. 
  2)  The product must be installed and activated in compliance with current electric
    systems standards. 
  3)  After installation inaccessibility to the terminals without using dedicated tools must
       be guaranteed 
  4)  Do not use the product for anything other than the indicated purpose. 
  5)  The product must be installed in an adequately protected closed electrical panel. 
  6)  In the supply network there must be a bipolar disconnection. 
  7)  In the electrical system upstream of the product must be installed a protection
  device against the overcurrents. 
  8)  Before accessing the connection terminals, make sure that the leads are not live. 
  9)  Do not connect or feed the product if any part of it is damaged.  
 10)  The product can be used in environments with Measurement Category III and 
  Pollution degree 2, according to the Standard EN 60730-1
  TECHNICAL FEATURES 
  • Power supply: 230 Vac (-15% ÷ +10%) 50/60 Hz  
  • Power consumption: 5,2 VA (0,7 W)  
  • Replaceable 3V lithium backup battery type CR1632 (duration: approximately 4 years)
  • Output: 1 normally open monostable relay 16 A / 250 V
  • Terminal block for cables with maximum cables section of 2.5 mm
2  
  • Storable programs: 120 events   
  • Bluetooth communication interface: BLE 5.1
     (active with mains power)
  • Operating frequency band: 2400-2483,5 MHz  
  • Maximum transmitted radiofrequency power: 4 dBm  
  • LED: 2 Operation status LED  
  • Keyboard: 1 key for configuring and forcing relay output ON/OFF
  • Operating temperature: -20°C ÷ 50°C  
  • Operating humidity: 20 ÷ 90%  non condensing 
  • Storage temperature: -20°C ÷ 70°C  
  • Insulation: reinforced between accessible parts (front) and all the other terminals
  • Actions of type: 1B  
  • Container: 1 DIN module
  • Protection degree: IP20 
3CONNECTION DIAGRAM 
Note:  the monostable relay 
switches only if the device 
is mains powered.
16A / 250Vac
2
3
4
information to users pursuant to art. 14 of the directive 
2012/19 / EU of the european parliament and of the council
of 4 july 2012 on waste electrical and electronic equipment (WEEE)
If the crossed-out bin symbol appears on the equipment or packaging,
this means the product must not be included with other general waste 
at the end of its working life.
The user must take the worn product to a sorted waste center,  
or return it to the retailer when purchasing a new one.
Products for disposal can be consigned free of charge (without any new purchase obligation)
to retailers with a sales area of at least 400 m
2, if they measure less than 25 cm.
An efficient sorted waste collection for the environmentally friendly disposal of the used device, or its 
subsequent recycling, helps avoid the potential negative effects on the environment and people’s health,
and encourages the re-use and/or recycling of the construction materials.
18 65
91
9LED SIGNALS 
The 2 LEDs on the device allow you to understand the operating status of the device, according to the types of switch on described in the table: 
  LED   Type of switch on      Operating status 
   GREEN 
         Steady on    Normal operation 
   Fast ashing         Connection with smartphone successful
    Short switch on  Low or no battery (replace the battery)       
    Short switch o         Time or date not congured
  RED 
    Steady on         Relay status ON 
    O        Relay status OFF 
    Short switch on         Relay status LOCK OFF 
    Short switch o         Relay status LOCK ON 
   Fast ashing         Anomaly (reset the device see BOX 4)
    + REDGREEN
    Fast alternating ashing        Device reboot 
    Simultaneous fast ashing        Keypad lock enabled (displayed when the key is pressed) 
    Simultaneous slow ashing        Anomaly (remove power from the device for at least 30 seconds and power it back on) 
In this condition, when mains power returns, the display will flash, the time 
start from 00:00 o’ clock of 01.01 and the relay stays in OFF position. In this 
case, to resume the normal operating, set time and date. 
Use only CR-1632 type batteries. 
  It is necessary to remove the batteries before the instrument is scrapped.
  In case of replacement, dispose of the batteries in the special 
        containers of separate waste collection.
Warning: before accessing the battery compartment, disconnect the power 
                supply
Warning:  in order not to lose carried out settings, it is necessary to ensure 
that the time for the battery replacement doesn’t exceed 60 seconds 
(in absence of power by means)
8DEPLETED BATTERY 
When the backup battery is close to empty, the green LED flashes briefly.
In this condition, replace the battery as soon as possible, by accessing the 
battery compartment, to avoid that, in case of blackout, the date and time 
are lost. 
7KEYBOARD OPERATION
The key on the device, depending on the type of pressure exerted, 
is used to perform the operations described in the table:
   Pressure type    Function
   Short pressure      Manual relay ON/OFF switching 
   Long pressure (> 3 sec)      Lock (or unlock) the switching of the relay  
   Prolonged pressur  (> 10 sec)     Reset settings: reset all settings to factory default
NOTE: If the keyboard lock has been set by the app, all key presses will be 
ignored. To unlock the device in case it is not possible to access the app, 
you need to remove and reapply power to the timer and reset the device 
(see Box 4). The keyboard remains unlocked for 30 seconds, which is 
enough time to perform the procedure to restore default settings.  
5INSTALLATION AND PRELIMINARY OPERATIONS 
6CONFIGURATION REMOTE CONTROL  
• The device is provided with inserted date, hour and backup battery.
• Install and connect the device respecting the connection diagrams shown 
   in this manual.
• Access the store of your smartphone, install and start the free memo – Vemer app.
• Check that the Bluetooth and the GPS of your smartphone are active and the consent 
   to the memo - Vemer App to be able to identify the position (GPS) is enabled 
   (adapt the settings on the smartphone such as to be able to perform this tracking; 
   for further information see the instructions of your smartphone). . 
     To configure the device using a smartphone, proceed as follows:
1. Start the    and press theApp  “+” key
    present on the Home page
2. Press the Bluetooth connection box and select 
    the Connect key
3. Find and select the  device in the “MICRO BT”  
    list to connect to the timer (the green LED 
    will start flashing quickly to indicate that it has
    happened connection between app and device).
 
    Notes: all the Bluetooth devices detected nearby 
    are displayed: select the device to be associated 
    from the list.  Each device is identified by the 
    product code (for example VE797200) and by 
    the serial number (for example 12340003) and
    the name of the model (for example MICRO BT).  
    Warning: make sure that the micro BT is mains
    powered, otherwise the Bluetooth interface is 
    not active and the device is not visible. 
4. Confirm   received on your phone the double Bluetooth pairing notification
    by entering the password to pair the micro BT with your phone (if not changed the
    password is 123456) and wait for synchronization with the device. 
5. After successfully completing the procedure, the app displays the initial page of the
    selected microBT .
    From this page it is possible
  a. Create new programs which will then be copied to the micro BT
  b. Change the micro BT settings
      c. View the parameters and associate an alias (name that identifies the device, 
      such as “external lights”) to the micro BT
      d. Manually control the relay output and activate the random switching function
   Note: The communication between app and micro BT is point-to-point. 
  This means that, even in the presence of multiple devices, the app can 
  communicate with only one at a time.
4DEVICE RESET 
     Perform a reset to delete the settings and programs entered and return the device 
     to factory settings. To reset, hold down the button (at least 10 seconds) until the LEDs
     start to flash alternately.
 Important: when the device is turned on for the first time or by performing 
                          a factory reset, the 
Bluetooth connection password is 123456
ONRelay
ON