List of existing communication objects and standard settings
ACTUATOR FUNCTIONAL UNIT
Communication objects and ETS parameters
C R W T = Communication; = Read; = Write; = Transmission; = Enable updateU
Number Name in ETS Function in ETS Description Length Flag
C R W T U
0 OUT ON/OFF (If the output is enabled as "Switching module") to switch the output ON/
OFF 1 bit X X
1 OUT Stair light (If the output is configured as “Stair light”) to control the output with timer 1 bit X X
2 OUT Block (If the Out 1 "Block" parameter is activated with "Block" function) to inhibit
the Output control from the bus 1 bit X X
3 OUT Force (If the Out 1 "Block" parameter is activated with "Forcing" function) to
force output to ON/OFF from the bus 2 bit X X
4 OUT Scenario (If the output "Scenario" parameter is on), to activate and, if required, store
(if the parameter is active) a scenario associated with the output 1 byte X X
5 OUT State (If the output is enabled as "Switching module” or “Stair light”) to know
the state of the output 1 bit X X X
6 OUT Logic 1
(If "1/2-object logic" is activated on the output) if a bit = 1 is sent to this
object the output will be activated when the "ON/OFF" object and the
"Logic 2" object, if present, are also activated (depending on the And/Or
conditions that are managed on these objects)
1 bit X X
7 OUT Logic 2
(If "1/2-object logic" is activated on the output) if a bit = 1 is sent to this
object the output will be activated when the "ON/OFF" object and the
"Logic 1” object are also activated (depending on the And/Or conditions
that are managed on these objects)
1 bit X X
Communication objects: default settings
Number Name in ETS Function in ETS Length Priority Flag
C R W T U
0 Output A ON/OFF 1 Bit Low X X
1 Output A Stair light (one-position stable Out) 1 Bit Low X X
2 Output A Block 1 Bit Low X X
3 Output A Forced 2 Bit Low X X
4 Output A Scenario 1 byte Low X X
5 Output A State 1 Bit Low X X X
6 Output A Logic 1 1 Bit Low X X
7 Output A Logic 2 1 Bit Low X X
C R T = Communication, = Read, W = Write, = Transmission, = Enable updateU
Standard communication object settings
Number of communication objects Max. number of group addresses Max. number of associations
8 254 255