Læs gratis den danske manual til Wachendorff LD4A05P0 (16 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 21 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 11 anmeldelser. Har du et spørgsmål om Wachendorff LD4A05P0, eller vil du spørge andre brugere om produktet?

Side 1/16
1
AIR PRESSURE STABILIZATION VENT (57.15)
2.25
X
Z
Y
GENERAL DESCRIPTION
The Large Display is a versatile display available as a DC volt, current, or
process meter with scaling, serial communications and dual relay outputs. The 5
digit displays are available in either 2.25" or 4" high red LED digits with
adjustable display intensities. The 2.25" high models are readable up to 130 feet.
The 4" high models are readable up to 180 feet. Both versions are constructed
of a NEMA 4X/IP65 enclosure in light weight aluminum.
All models also come with dual Form C relay outputs and RS232 / RS485
serial communications.
SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and
corresponding literature, or on equipment, must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment connected to
it. If equipment is used in a manner not specied by the manufacturer, the
protection provided by the equipment may be impaired.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
LD2A 2.25" High 5 Digit Red LED Volt/Current Meter w/
Relay Output and RS232/RS485 Serial Comms LD2A05P0
LD4A 4" High 5 Digit Red LED Volt/Current Meter w/
Relay Output and RS232/RS485 Serial Comms LD4A05P0
LD Plug Panel Meter Plug for LD models
(NOT included in LD Product UL File) LDPLUG00
SPECIFICATIONS
1. DISPLAY: 5 digit, 2.25" (57 mm) or 4" (101 mm) intensity adjustable Red LED
(-99999 to 99999)
2. :POWER REQUIREMENTS
AC POWER: 50 to 250 VAC 50/60 Hz, 26 VA
DC POWER: 21.6 to 250 VDC, 11 W
DC Out: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/VDC
+24 VDC @ 50 mA if input voltage is less than 50 VDC
Isolation: 2300 Vrms for 1 min. to all inputs and outputs
3. INPUT RANGES: Jumper Selectable
D.C. Voltages: 200 mV, 2 V, 20 V, 200 V, 10 V
D.C. Currents: 200 A, 2 mA, 20 mA, 200 mA
D.C. Process: 4 to 20 mA, 1 to 5 VDC, 0/1 to 10 VDC
4. OVERRANGE/UNDERRANGE INDICATION:
Input Overrange Indication: OLOL”.
Input Underrange Indication: ULUL”.
Display Overrange/Underrange Indication: ..... .....”/“-
2.25" & 4" HIGH RED LED DIGITS
PROGRAMMABLE SCALING AND DECIMAL POINTS
PROGRAMMABLE USER INPUT
DUAL 5 AMP FORM C RELAY
ALUMINUM NEMA 4X/IP65 CASE CONSTRUCTION
RS232/RS485 SERIAL COMMUNICATIONS
UNIVERSALLY POWERED
MODEL LD - LARGE DC VOLT/CURRENT/PROCESS DISPLAY
DIMENSIONS In inches (mm)
Bulletin No. LDA-C
Drawing No. LP0673
Released 09/09
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
INPUT
RANGE
INPUT
IMPEDANCE
MAX
INPUT
SIGNAL
RESOLUTION TEMP.
COEFFICIENT
200 mV 0.1% of span 1.027 M75 VDC 10 Vμ70 ppm /°C
2 V 0.1% of span 1.027 M75 VDC 0.1 mV 70 ppm /°C
20 V 0.1% of span 1.027 M250 VDC 1 mV 70 ppm /°C
10 V
200 V
0.1% of span
0.1% of span
538 K
1.027 M
30 V
250 VDC
1 mV
10 mV
70 ppm /°C
70 ppm /°C
ACCURACY @
23 C LESS
THAN 85% RH
INPUT
RANGE
INPUT
IMPEDANCE
MAX
INPUT
SIGNAL
RESOLUTION TEMP.
COEFFICIENT
200 μΑ 0.1% of span 1.111 K15 mA 10 nA 70 ppm /°C
2 mA 0.1% of span 111 50 mA 70 ppm /°C0.1 Aμ
20 mA 0.1% of span 11 150 mA 1 Aμ70 ppm /°C
200 mA 0.1% of span 1 500 mA 10 Aμ70 ppm /°C
ACCURACY @
23 C LESS
THAN 85% RH
22 (558.8)
12 (304.3)
Z (Center)
7.875 (200)26 (660.4)LD4A05P0
4 (101.6)16 (406.4)LD2A05P0
Y (Height)X (Length)
PART
NUMBER
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
INPUT RANGE SELECT RANGE
4 - 20 mA Use the 20 mA range
1 - 5 VDC Use the 10V range
1 - 10 VDC Use the 10V range
C
C
C
C
C
US LISTED
US LISTED
US LISTED
US LISTED
US LISTED
UL
R
51EB
IND. CONT. EQ.
C
C
C
C
C
US LISTED
US LISTED
US LISTED
US LISTED
US LISTED
UL
R
LABORATORY EQUIPMENT
3RSD
2
5. A/D CONVERTER: 16 bit resolution
A/D Conversion Rate: 6 readings/sec.
6. DISPLAY RESPONSE TIME: 500 msec min.
7. : USER INPUT
Software selectable pull-up (8.6 K ) or pull-down resistor
(3.9 K ) that determines active high or active low input logic.
Trigger levels: VIL = 1.0 V max; VIH = 2.4 V min; VMAX = 28 VDC
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
8. COMMUNICATIONS:
Type: RS485 or RS232
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Data: 7/8 bits
Parity: no, odd or even
Baud Rate: 300 to 38.4 K
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
9. MEMORY: Nonvolatile E2PROM retains all programming parameters and
max/min values when power is removed.
10. :OUTPUT
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8
H.P. @ 120 VAC (inductive load)
Life Expectancy: 100,000 minimum operations
Response Time:
Turn On Time: 4 msec max.
Turn O Time: 4 msec max.
11. ENVIRONMENTAL CONDITIONS:
Operating temperature: 0 to 50 °C
Storage temperature: -40 to 70 °C
Operating and storage humidity: 0 to 85% max. RH (non-condensing)
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g’s (1 g relay).
Shock According to IEC 68-2-27: Operational 30 g’s (10 g relay), 11 msec
in 3 directions.
Altitude: Up to 2,000 meters
12. CONNECTIONS:Internal removable terminal blocks
Wire Strip Length: 0.4" (10 mm)
Wire Gage: 24-12 AWG copper wire
Torque: 5.3 inch-lbs (0.6 N-m) max.
Cable Diameter: Outside diameter must be 0.181" (4.6 mm) to 0.312" (7.9
mm) to maintain NEMA 4 rating of cord grips.
13. CONSTRUCTION: Aluminum enclosure, and steel side panels with textured
black polyurethane paint for scratch and corrosion resistance protection. Meets
NEMA 4X/IP65 specications. Installation Category II, Pollution Degree 2.
14. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
File # E179259, UL61010A-1, CSA C22.2 No. 61010-1
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating, UL50
IECEE CB Scheme Test Report #E179259-A3-CB-1
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating, IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Notes:
1. Criterion A: Normal operation within specied limits.
2. Criterion B: Temporary loss of performance from which the unit self-
recovers.
15. :WEIGHT
LD2A05XX - 4.5 lbs (2.04 kg)
LD4A05XX - 10.5 lbs (4.76 kg)
1.0 INSTALLING THE METER
Class AEN 55011Emissions
0.5 cycle
Criterion AEN 61000-4-11
Emissions:
Voltage dip/interruptions
3 V/rms
Criterion BEN 61000-4-6RF conducted interference
1 kV L-L,
Criterion AEN 61000-4-5Surge
1 kV signal
2 kV power
Criterion BEN 61000-4-4Fast transients (burst)
2 kV L&N-E power
10 V/m
Criterion BEN 61000-4-3Electromagnetic RF elds
8 kV air discharge
4 kV contact discharge
Criterion BEN 61000-4-2Electrostatic discharge
Immunity to Industrial Locations:
INPUT RANGE JUMPER
This jumper is used to select the proper input range. The input range selected
in programming must match the jumper setting. Select a range that is high
enough to accommodate the maximum signal input to avoid overloads. To
access the jumper, remove the side cover of the meter.
Warning: Exposed line voltage exists on the circuit boards.
Remove all power to the meter and load circuits before accessing
inside of the meter.
2.0 SETTING THE JUMPERS
RANGE SELECT
6542 31
TBC
20 V/200 V
200 MV/2 V
10 V
200 µA
200 MA
20 MA
2 MA
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating
temperature. Placing the unit near devices that generate excessive heat should
be avoided. The unit should only be cleaned with a soft cloth and neutral soap
product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging process of
the front overlay. Do not use tools of any kind (screwdrivers, pens, pencils, etc.)
to operate the keypad of the unit.
MOUNTING INSTRUCTIONS
This display is designed to
be wall mounted or
suspended from a ceiling
truss or other suitable
structure capable of
supporting the LDA.
Caution should be
exercised when hanging
the display to provide for
the safety of personnel. If
hanging the LDA, run the
suspension cables (or chains)
through the mounting bracket
holes. For wall mounting use
#10-32 size bolts.
MOUNTING HOLE (.281")
MUST BE
CONNECTED TO
TERMINAL #3 (TBA)