Canarm CEPD140-4 Manual


Læs gratis den danske manual til Canarm CEPD140-4 (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 2 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 1.5 anmeldelser. Har du et spørgsmål om Canarm CEPD140-4, eller vil du spørge andre brugere om produktet?

Side 1/4
WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
CAUTION
CLEANING & MAINTENANCE
OPERATION
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the
dusting brush attachment.The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive
or unusual noises, replace the motor with the exact service motor. The impeller should also be replaced.
Cod0060302209
ModelCEPD140-4
a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power
from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and
standards, including fire-rated construction codes and standards.
d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to
prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by
the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE), and the local code authorities.
e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f ). Ducted fans must always be vented to the outdoors.
g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit
(ceiling installation only).
h). This unit must be grounded.
i). Not for Use in Kitchens.
j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or
ceilings or into attics, crawl spaces, or garages.
k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control Device.
l). The fan must not be installed in a ceiling thermally insulated to a value greater than R40.
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
*The manual in electronic format can be download in our company web, or obtained from our dealer.
WARNING -TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
See “CONNECT ELECTRICAL WIRING” for details.
The control box, located inside the fan housing:
(1) The low airflow knob adjusts the lower airflow from 40CFM up to the air flow
rate of the high fan speed (For CEPD140-4, the high fan speed is determined by
the toggle switch setting). The fan will not work when the knob turned between
OFF-40CFM.
(2) The time delay knob is adjustable from 3 to 30 minutes and will switch the fan
to the low speed setting after the switch is turned off for the set period of time.
(3) The toggle switch will adjust the upper fan speed setting from 80 to 140 CFM.
(Only for CEPD140-4)
Fan will run at the user-adjustable airflow rate continually;
turn on the switch, fan will turn to high speed;
turn off the switch, fan will continue to run at the certified airflow rate until the
user-adjustable time delay has passed, and then will automatically change to the
user-adjustable airflow rate.
VENTILATION FANS
1 2 3
Toggle switch
(only for CEPD140-4)
Control Box
Low airflow
knob
is the position of switch
time delay
knob
140
1 2 3
Switch position
Airflow (CFM) 110
1 2 3
90
1 2 3
80
1 2 3
TS
Max.
40CFM
30min
10min
20min
3min
140
1 2 3
Switch
position
Airflow (CFM) 110
1 2 3
90
1 2 3
80
1 2 3
1 2 3
OFF
50%
70%
CEPD150
CEPD200
www.canarmna.com
CANARMNA
1. Do not use in a cooking area.
2. Two ways to connect ductwork to a factory-shipped unit.
2
ROOF CAP*
(with built-in
damper)
ROUND
DUCT*
WALL CAP*
(with built-in
damper)
* Purchase
separately
POWER
CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct
joints with
tape.
Keep duct
runs short
PLAN THE INSTALLATION
ASSEMBLY INSTRUCTIONS
1.Sliding hanger bars have been provided, which allow the housing to be
positioned accurately anywhere between the framing. The bars span up to 24 in.
and can be used on all types of framing: I-joist, standard joist, and truss construc-
tion. Slide hanger bars onto housing and adjust as needed to fit between framing.
2.Extend the hanger bars to the width of the framing. Position the ventilator with
the bottom edge of the hanger bar tabs are flush with the bottom edge of the
framing, holding the ventilator in place.Secure hanger bars to framing using one
screw on each end of hanger bar.Select a proper hole and secure the hanger
bars together using one screw.
Hanger Bar
screw
3.INSTALL ROUND DUCTWORK
Connect the round ductwork (not included) to the damper/duct connector,and run
the ductwork to a roof or wall cap (not included). Using tape (not included),
secure all the ductwork connections so that they are air tight.
The ducting from this fan to the outside of building has a strong effect on the air
flow, noise and energy use of the fan.
Use the shortest, straightest duct routing possible for best performance, and
avoid installing the fan with smaller ducts than recommended. Insulation around
the ducts can reduce energy loss and inhibit mold growth. Fans installed with
existing ducts may not achieve their rated air flow.


Produkt Specifikationer

Mærke: Canarm
Kategori: Ikke kategoriseret
Model: CEPD140-4

Har du brug for hjælp?

Hvis du har brug for hjælp til Canarm CEPD140-4 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Canarm Manualer

Canarm

Canarm CEPD140-4 Manual

17 September 2025
Canarm

Canarm CNP100 Manual

17 September 2025
Canarm

Canarm CBFI300 Manual

17 September 2025
Canarm

Canarm C50 Manual

17 September 2025
Canarm

Canarm CNPD100-3 Manual

17 September 2025
Canarm

Canarm CEP110 Manual

17 September 2025
Canarm

Canarm CP50 Manual

17 September 2025
Canarm

Canarm P14-4M Manual

16 September 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Vulcan

Vulcan VBP15SL Manual

17 September 2025
Rocktrail

Rocktrail IAN 463536 Manual

17 September 2025
Kimo

Kimo KNT 320 Manual

17 September 2025
Vestil

Vestil LPRO-36-16-4 Manual

17 September 2025
Vestil

Vestil CPC-20 Manual

17 September 2025
Vestil

Vestil CANT-3648 Manual

17 September 2025
InLine

InLine 16277S Manual

17 September 2025
Vestil

Vestil H-75-LD Manual

17 September 2025