Læs gratis den danske manual til Crestron CLX-2DIMU8-277 (2 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 10 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 5.5 anmeldelser. Har du et spørgsmål om Crestron CLX-2DIMU8-277, eller vil du spørge andre brugere om produktet?

Side 1/2
Quick Start
Control up to eight channels of dimmed lighting using the Crestron®
CLX-2DIMU8-277 module. The CLX-2DIMU8-277 supports two 277
VAC line power inputs and can dim LED, incandescent, magnetic
low-voltage, electronic low-voltage, and 2-wire dimmable fluorescent
lighting loads. The CLX-2DIMU8-277 auto-detects the dimmed load
type and selects the appropriate operating mode for each channel.
The CLX-2DIMU8-277 pairs with the CLT-2DIMU8-277 terminal block to
facilitate simple wiring. The CLT-2DIMFLV8-277 ships separately from
wiring prior to the installation and setup of the CLX-2DIMFLV8-277.
The CLT-2DIMU8-277 and CLX-2DIMU8-277 install in a CAEN enclosure
as part of a complete Crestron centralized lighting control system.
Check the Box
Item Qty
CLX-2DIMFLV8-277 1
Cable, Interconnect (P/N 4500250) 1
Screw, 8-8B x 1/4 in., Pan Head, Phillips (P/N 2007277) 4
CLT-2DIMFLV8-277 1
Label, Terminal Block, CLT-2DIMFLV8, 277V, Left
(P/N 4524249)
1
Label, Terminal Block, CLT-2DIMFLV8, 277V, Right
(P/N 4524250)
1
Screw, 8-8B x 1/4 in., Pan Head, Phillips (P/N 2007277) 2
Installation Overview
Unless otherwise indicated, the lighting system specified in this guide
is modular, requiring assembly in the field by a licensed electrician in
accordance with all national and local codes.
If an assembled UL® Listed panel is required, Crestron offers this
service through its UL Listed panel shop. This includes complete
in-factory system configuration and assembly by Crestron for an
additional fee.
WARNING:
The CLT-2DIMU8-277 and CLX-2DIMU8-277 may be powered
from multiple circuit breakers.
A licensed electrician must mount the CLT-2DIMU8-277 and
CLX-2DIMU8-277 into the CAEN enclosure in accordance with all
national and local codes.
When connecting to an arc fault breaker, ensure the load does
not exceed 1,000 watts total. Crestron certified breakers have a
2,000-watt limit.
CAUTION: This equipment is for indoor use only and needs to be air
cooled. Mount in a well-ventilated area. The ambient temperature
must be 32° to 104 °F (0° to 40 °C). The relative humidity must be 0%
to 90% (noncondensing).
IMPORTANT NOTES: When controlling magnetic low-voltage
transformers:
Do not use a CLX-2DIMU8-277 module for switching or dimming
large magnetic transformers (>100 VA).
Do not connect more than eight magnetic transformers on any
one output, regardless of lamp wattage.
Do not hot plug transformers or add or remove bypass jumpers
while the output channel is energized.
Do not mix magnetic and electronic transformers on the same
output channel.
Failure to follow the guidelines above can lead to damage of the
dimmer module and transformers.
CLT-2DIMU8-277 and CLX-2DIMU8-277 in a Single-Wide CAEN
Enclosure
Ground bus CLT- terminal
block
CLX- module
CLT-2DIMU8-277 and CLX-2DIMU8-277 in a Double-Wide CAEN
Enclosure
Ground bus
CLT- terminal block CLT- terminal blockCLX- modules
Install and Wire the Terminal Block
Install the Terminal Block
Install the CLT-2DIMU8-277 into the lowest available space in the
CAEN enclosure. Mount additional CLT-2DIMU8-277s into the spaces
above it in ascending order.
The CLT-2DIMU8-277 installs along the left side of a single-
wide enclosure and along the outside edges of a double-wide
enclosure. Refer to the CAEN Installation Guide (Doc. 5940) at
www.crestron.com/manuals for mounting information.
1. Turn the power OFF at the circuit breaker(s) or fuse panel(s).
2. Remove the backing from the terminal block label. Align the holes
on the label with the holes on the enclosure and attach the label
to the enclosure.
Use the Left Terminal Block Label when mounting the
CLX-2DIMU8-277 into a single-wide CAEN enclosure or into
the left side of a double-wide CAEN enclosure
Use the Right Terminal Block Label when mounting the
CLX-2DIMFLV8-277 into the right side of a double-wide CAEN
enclosure.
3. Align the CLT-2DIMU8-277 with the terminal block label. The
colors on the CLT-2DIMU8-277 match the colors on the terminal
block label. Secure the CLT-2DIMU8-277 to the enclosure using
two 8-8B x 1/4 in. screws. The wiring label lies beneath the
terminal block.
CAUTION: Bypass jumpers are provided to test the circuits and to
protect the module during installation. When properly secured by
five screws, the jumpers on the black and red sections of the terminal
block short (connect) the line in to the dim out so that the circuit is
energized. Do not remove the bypass jumpers until all feed and load
wiring has been completed, the circuit has been tested for electrical
faults, and the module has been installed. Refer to “Module Installation
and Wiring” for details.
Do not remove the two jumpers on the white sections of the terminal
bock that tie the neutral in and neutral out wires.
Wire the Terminal Block
Connect the feed (Line and Neutral) and the load (controlled circuit)
wires to the terminal block. For 2-feed systems, the two power feeds
can be different phases. Follow the labeling on the wiring label.
NOTE: Use copper conductors only, rated 75 °C or greater.
When connecting wires:
Use 14-10 AWG wire.
Strip wire to 1/2 in (13 mm).
Tighten the terminal blocks to 9 in-lb.
Connect the Ground wires to the ground bus inside the enclosure:
Strip wire to 1/2 in (13 mm).
Tighten 14-10 AWG wire to 35 in-lb.
Tighten 8 AWG wire to 40 in-lb.
Tighten 6-4 AWG wire to 45 in-lb.
Connect the Feed and Load wires to the CLT-2DIMU8-277
LINE 1
Line power from a
15 or 20 A circuit
breaker
N IN 1
Neutral from the
circuit breaker
N IN 2
Neutral from the
circuit breaker
GND
Ground from the
circuit breaker
Bypass
jumpers
Terminal
block
Dim and
Neutral to
loads
Left-side
wiring label
LINE 2
Line power from a
15 or 20 A circuit
breaker
Ground
bus
Module
location
label
NOTE: When wiring the terminal block on right-side double-wide
enclosures, the connection points on the label are reversed.
Test the Terminal Block Wiring:
1. Turn the power ON at the circuit breaker(s) or fuse panel(s).
2. Verify that the circuit breakers do not trip.
3. Verify that the power is delivered to the proper loads.
4. Repeat Steps 1-3 for the other circuit breaker(s) or fuse panel(s).
Install and Wire the Dimming Module
The dimming module installs along the right side of a single-wide
CAEN enclosure and side-by-side in the center of a double-wide CAEN
enclosure. Install the CLX-2DIMU8-277 next to the CLT-2DIMU8-277
and in the lowest available space. Refer to the CAEN Installation Guide
(Doc. 5940) at www.crestron.com for mounting information.
CAUTION: The module contains electrostatic sensitive devices (ESDs);
the unit must be handled from the metal chassis. Do not touch the PC
board or components.
NOTE: Install the modules after the enclosure has been completely
wired. Refer to “Install the Terminal block” for details.
Install the Dimming Module
1. Turn the power OFF at the circuit breaker(s) or fuse panel(s).
2. Secure the dimming module to the enclosure using four
8-8B x 1/4 in. screws.
The wires on the CLX-2DIMU8-277 should exit and face the
left when installing in a single-wide CAEN enclosure or on the
left side in a double-wide CAEN enclosure.
The wires on the CLX-2DIMU8-277 should exit and face the
right when installing on the right side in a double-wide CAEN
enclosure
3. Connect the prestripped wires from the module to the terminal
block. Each wire exits the module directly in line with, and is the
same color as, the terminal to which it should be connected.
Wires are prestripped to 1/2 inch (13 millimeters). Tighten to
9 in-lb.
NOTE: The CLX-2DIMU8-277 is powered from the LINE 1
connection.
Wiring the Terminal Block to the Module
(Single-Wide and Left-Side Double-Wide Enclosures)
Black from breaker
Black from breaker
White from panel
White from panel
Red to loads
Red to loads
White to loads
White to loads
Install the Module Interconnect Cable (Optional)
If multiple modules are installed within an enclosure, use the module
interconnect cable (supplied) to pass control system communication
to the module. The illustration that follows shows the area within a
double-wide enclosure where the corners of four modules meet.
NOTE: One wire on the module interconnect cable may be a different
color from the rest. The color has no bearing on its orientation during
installation.
Using Module Interconnect Cable to Wire One Module to Another
Module interconnect
cable attached
Connection
not made
CLT-2DIMU8-277/CLX-2DIMU8-277
Terminal Block and Module


Produkt Specifikationer

Mærke: Crestron
Kategori: Ikke kategoriseret
Model: CLX-2DIMU8-277
Type: Lysdæmper
Vekselstrømsindgangsspænding: 277 V
Bredde: 176 mm
Dybde: 87 mm
Højde: 194 mm
Relativ luftfugtighed ved drift (H-H): 10 - 90 %
Driftstemperatur (T-T): 0 - 40 °C

Har du brug for hjælp?

Hvis du har brug for hjælp til Crestron CLX-2DIMU8-277 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Crestron Manualer

Crestron

Crestron HZ2-AUX Manual

7 Oktober 2025
Crestron

Crestron PW-2407WUL Manual

29 September 2025
Crestron

Crestron C2N-UNI8IO Manual

28 September 2025
Crestron

Crestron CLXI-4HSW4 Manual

24 September 2025
Crestron

Crestron GLD-LED-50W Manual

24 September 2025
Crestron

Crestron TPS-4LW Manual

23 September 2025
Crestron

Crestron Zūm Manual

23 September 2025
Crestron

Crestron SIMPL Manual

23 September 2025
Crestron

Crestron UC-FCM-T Manual

23 September 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Intermatic

Intermatic OP5BK24 Manual

4 November 2025
Sony

Sony SNC-EM601 Manual

4 November 2025
Sony

Sony SNC-VM630 Manual

4 November 2025
Zotac

Zotac ZBOX MI525 Manual

4 November 2025
DS18

DS18 SLG-RSUB10XLLD Manual

4 November 2025
ANCEL

ANCEL AJ400 M Manual

4 November 2025