Eastron SDM230-Modbus Manual

Eastron Måling SDM230-Modbus

Læs gratis den danske manual til Eastron SDM230-Modbus (13 sider) i kategorien Måling. Denne vejledning er vurderet som hjælpsom af 18 personer og har en gennemsnitlig bedømmelse på 4.9 stjerner ud af 9.5 anmeldelser. Har du et spørgsmål om Eastron SDM230-Modbus, eller vil du spørge andre brugere om produktet?

Side 1/13
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -1
SDM230-Modbus
Single-Phase Two Module DIN rail Meters
Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounng 35 mm
100A direct connecon
Beer than Class 1 / B accuracy
User Manual V1.4
2015
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -2
Applicaon
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residenal, Ulity and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communicaon port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Specicaon
General Specicaons
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) A 10
Max. Current (Imax) 100A
Mini Current (Imin) 5A 0.
Starting current 0.4% of Ib
Power consumpon <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
1000/100/10/1 imp/kWh/kVarh (congurable)
Display LCD with blue backlit
Max. Reading 999999.9kWh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Acve power 1% of range maximum
Reacve power 1% of range maximum
Apparent power 1% of range maximum
Acve energy Class 1 IEC62053- 21
Class B EN50470-3
Reacve energy 1% of range maximum