Læs gratis den danske manual til Emko ATS-10 (7 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 20 personer og har en gennemsnitlig bedømmelse på 3.8 stjerner ud af 10.5 anmeldelser. Har du et spørgsmål om Emko ATS-10, eller vil du spørge andre brugere om produktet?
Side 1/7

Description
Operation
The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- The ledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
- TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellow ledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgota TEST modefeature. Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning. Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16

2
Automatic Transfer Switch, 72x72 DIN Size
Specifications
EquipmentUse Electricalcontrolequipmentforgeneratingsets
Housing&Mounting 72mmx72mmx95mm(includingconnectors)DIN43700plastichousingforpanelmounting
PanelCut-out 69mmx69mm
Protection NEMA4X(IP65atfrontpanel,IP20atrearside)
Weight Approximately0.27kg
EnvironmentalRating Standard,indooratanaltitudeoflessthen2000meterswithnon-condensinghumidity
Operating/Storage Temperature -25ºCto+70ºC/-40ºCto+85ºC
Operating/StorageHumidity 90%max.(Non-condensing)
InstallationOverVoltageCat. IIappliances,portableequipment
PollutionDegree II,Normalofficeorworkplace,non-conductivepollution
ModeofOperation Continuous
EMC EN-61000-6-4,EMCgenericemissionstandardforindustrialequipment
EN-61000-6-2,EMCgenericimmunitystandardforindustrialequipment
ElectricalSafety EN-61010-1,safetyrequirementsforelectricalequipmentformeasurement,controland
laboratoryuse
BatterySupplyVoltage( )Z8-32V max.Operatingcurrentis240mAZ
CrankingDropouts Batteryvoltagecanbe0V formax.100msnduringcranking(batteryvoltageshouldbeZ
atleastnominalvoltagebeforecranking)
MainsVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
GeneratorVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
Display 4Digits,7segmentsLEDdisplayshowing:
MainsVoltage(Phase-PhaseandPhase-Neutral)
AlternatorVoltage.( )
IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1)
ProgramParameters
StatusIndicators TEST ModeLED
MainsContactorClosedLED
GeneratorContactorClosedLED
ContactSensingInputs LoadGeneratorSignal(NO)
EngineRunningSignal(NO)
RelayOutputs RemoteStartRelay(1NO+1NC.12A@32V )Z
MainsContactorRelay(1NC.5A@250V )V
GeneratorContactorRelay(1NO.5A@250V )V
MainsVolgageOkayLED
GeneratorRunningLED
PROGModeLED
Produkt Specifikationer
Mærke: | Emko |
Kategori: | Ikke kategoriseret |
Model: | ATS-10 |
Har du brug for hjælp?
Hvis du har brug for hjælp til Emko ATS-10 stil et spørgsmål nedenfor, og andre brugere vil svare dig
Ikke kategoriseret Emko Manualer
16 Juli 2025
25 Juni 2025
23 Juni 2025
29 December 2024
29 December 2024
29 December 2024
29 December 2024
29 December 2024
29 December 2024
31 August 2024
Ikke kategoriseret Manualer
- Belena
- MAX LINER
- Zeiss Ikon
- Orima
- Metabolic Devices
- TacTic
- PowerColor
- BSS Audio
- Cocraft
- Amfra
- Veise
- Morris
- Labpano
- Kopul
- Cane Creek
Nyeste Ikke kategoriseret Manualer
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025
22 August 2025