Læs gratis den danske manual til Emko EAOM-36 (8 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 3.7 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Emko EAOM-36, eller vil du spørge andre brugere om produktet?

Side 1/8
Features
Controls
FailMonitoring
EAOM-36ManualStartUnitusemicroprocessorbasedtechnologytoprovideintegratedmanualstartand
faultprotectioninawiderangeofengineapplications. Themoduleishousedin72x72DINsize.Themoduleis
usedtostartandstoptheengine,indicatingtheoperationalstatusandfaultconditions. Automaticallyshutting
downtheengineandindicatingtheenginefailurebyaflashingLED.Usercancontroltheengineviaatwoposition
keyswitchandpushbuttonsmountedonthefrontpanelorwithremoteinput.
Themodulehasthreeapplicationfeature;'Generator','Pump'or'FirePump'.(canbeselectedfrom
parameterP00).
Themodulecanconnectdirectlywithengine,thankstohighcurrentrelayoutputs.
Themodulehastwofeatureforfuel.Oneof“energizetorun”theother“energizetostop”.Usercanselectthe
featurefromprogramparameters.
The module protect the engine against fault conditions. If a fault condition occurred, the module indicate the fault
condition and shut-down the engine.
If the key switch is OFF position the module has zero power consumption to save energy. The module energizes
when the key switch position is getting ON position. If Satart button is pressed, the Conf. Out relay output (if selected
preheat output) will activate until the preheat delay is expired.
Press Start button for starting the engine. When engine is running, module will stop the cranking.
Press Stop button for stoping the engine. After pressing the stop button, the engine will keep running until cooling
time(P21) is expired.
Also the module has remote start facility. Please select suitable type of remote start for your application from
program parameters. If remote start input is active the module will start the engine. If remote start is passive the unit will
stop the engine after cooling time is expired.
The module will check the alarms after safety on timer is expired.
Under one of this fault conditions the module will stop the engine;
- Over speed (generator application),
- Under speed(generator application),
- High Temperature,
- Low Oil Pressure,
- Shutdown (if one of conf. input selected shutdown and activated).
To reset the fault, turn the key switch to the OFF position for a few seconds.
The Charge Failure is a warning alarm so the engine continue to work under this failure condition. Also this input
supplying charge alternator excitation current.
Shutdown the engine;
If the engine fuel type is “energize to stop”, press Stop button until the engine comes to rest. After that select OFF
position of the key switch.
If the engine fuel type is “energize to run”, select OFF position of the key switch.
On the Fire Pump application; If a fault condition occurred, the module will not stop the engine.
The engine will be stopped only when the stop button was pressed or the remote stop signal was detected.
Important note:
Manual and Remote Start with Key Switch, 72x72 DIN SizeUnit
DesignedForGenerator,Pump&FirePump Applications
Remotestart/stopcapabilitywithzeropowerconsumption
Enginestartandstop
Automaticshutdownonfaultcondition
Providesalarmandstatusinformation
Alarmandshutdowninputs
Provideschargealternatorexcitationcurrent
Lamptestfunction
Oilpressure
Enginetemperature
Overspeed&Underspeed(generatorapplication)
Chargingalternator
Conf.Input-1&2
Enginefuelorstopsolenoid
Startermotor
Preheat,simulatefuelsolenoid,externalalarm
horn,alarmorloadcontactorout
IntroductionBrochure.ENGEAOM-36R01V0612/17
START
Hz./
RPM
CHARGINGFAIL
~ ~
~~~~
HIGHTEMPERATURE
LOWOIL PRESSURE
FAILEDTOSTART
SPEED
FAILURE
0
I
EAOM-36
STOP
RPM
ProgramParametersforGenerator Application
1-Whenthe-BATTERY appliedtoRem.startinput(terminal-11),
theenginestartcranking.(leavekeyswitch“1”position)
2-Whenthe+BATTERY appliedto+BAT input(terminal-3),
theenginestartcranking.(leavekeyswitch“1”position)
0-Disable. Thestart/stopbutonisused. (leavekeyswitch“1”position)
ProgNo
ParameterName
Unit Limits Default
P 00
ApplicationSelection(Generator,Pump,FirePump) GEn,PUP,FPU GEn
P 01
P 02
P 04
P 06
P 07
P 08
P 09
FrequencyLowerLimit
FrequencyUpperLimit
-
Hz.
Hz.
30.0-75.0
30.0-75.0
47.0
53.0
HornDuration Sec. 0=Cont.1-999 30
Nominal AlternatorFrequency Hz. 30.0-75.0 50.0
NominalSpeed Rpm 500-5000 1500
Stop/FuelSolenoidSelection - StoP -FUEL FUEL
StopSolenoidEnergising Time Sec. 1-99 20
CrankDisconnectonGen.Frequency Hz. 25.0-75.0 30.0
P 10
CrankDisconnectonCharge AlternatorVoltage - diS-EnAb diS
P 11
CrankDisconnectonOilPressure
- 0=diS1-2 1
P 12
NumberofStarting Attempts Number 1-10 3
P 13
Starting AttemptDuration Sec. 5-99 5
P 14
OilPressureBypass Time Sec. 0-99 30
SafetyOnDelay
P 15
Sec. 0-99 10
FrequencyFaultControlDelay Sec. 0.0-10.0 3.0
P 16
P 17
EngineRunning TimeValue&NewEngineRunning Time Hour 0-9999 0
RemoteStartSelection:
P 18
P 19
Conf.Out Type:
- diS
-
0-4
P 20
Conf.Input1
0- Onlyhorntemporary,observationcontinuously
1- Onlyhornpermanent,observationcontinuously
2- Enginestop,observationcontinuously
3- Onlyhorntemporary,observationwhileenginerunning
4- Onlyhornpermanent,observationwhileenginerunning
5- Enginestop,observationwhileenginerunning
P 22
Conf.Input2
0- Onlyhorntemporary,observationcontinuously
1- Onlyhornpermanent,observationcontinuously
2- Enginestop,observationcontinuously
3- Onlyhorntemporary,observationwhileenginerunning
4- Onlyhornpermanent,observationwhileenginerunning
5- Enginestop,observationwhileenginerunning
Password 0-9999 0-
P 03
P 05
0-5 0
0-5 0
-
-
0=diS1-2
2
Manual and Remote Start with Key Switch, 72x72 DIN SizeUnit
!
Warning:P16RemoteStartSelectionparameteroption‘2’ cannotbeusedwithstopsolenoidtypegenerators.
Cooling Time Sec. 0(dis)-3600 0
P 21
0- AlarmOut,1-HornOut,
2-PreheatOut,3-SimulateFuelSolenoidOut,
4-LoadContactorOut
0
0-Disable
1-Enable(always)
2-Enable(onlybeforestart)


Produkt Specifikationer

Mærke: Emko
Kategori: Ikke kategoriseret
Model: EAOM-36

Har du brug for hjælp?

Hvis du har brug for hjælp til Emko EAOM-36 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Emko Manualer

Emko

Emko EAOM-19 Manual

8 September 2025
Emko

Emko ESM-9450 Manual

8 September 2025
Emko

Emko EAOM-71 Manual

8 September 2025
Emko

Emko EAOM-9F Manual

8 September 2025
Emko

Emko TRANS MAINS Manual

8 September 2025
Emko

Emko ES-7750 Manual

8 September 2025
Emko

Emko DT-9910 Manual

8 September 2025
Emko

Emko ESM-3770 Manual

8 September 2025
Emko

Emko ESM-3721 Manual

8 September 2025
Emko

Emko Trans-MidiAUTO Manual

7 September 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Daewoo

Daewoo AVS1425 Manual

13 September 2025
Tineco

Tineco iFloor 2 Manual

13 September 2025
Varta

Varta CellPac LITE Manual

13 September 2025
Daewoo

Daewoo COL1317 Manual

13 September 2025
Systemair

Systemair Airline H-106 Manual

13 September 2025
Daewoo

Daewoo AVS1350 Manual

13 September 2025
Daewoo

Daewoo AVS1411 Manual

13 September 2025