ESM-1520-N
P
5
2.5 Pane l Mounting
2.2 Installation onto the Rail
cDuring installation onto the rail, care should be taken to avoid injury from
mechanical part of the system. These precautions for the safety of the person
who does the rai mounting.
The unit is designed for rail mounting.
1- Put into the unit upper side of the
rail properly.
2- Pull down the rail lock apparatus
via a screw driver.
3.-Push the unit from the underside
for mounting to the rail.
2.3 Removing from the Rail
c
1- Pull down the rail lock apparatus
via a screw driver.
ull up the unit to remove from the
rail.
2- Pull the unit from the underside to
seperate the rail lock apparatus from
the rail
3.- P
Before starting to remove the unit from the rail, power off the unit and the
related system.
6
Supply Voltage I nput
3. Electrical Wiring Diagram
3.1 Supply Volta ge Inp ut Connection of the Device
1
NL
2
Y
c
a
Make sure that the power supply voltage is same indicated on the instrument.
Switch on the power supply only after that all the electrical connection have been completed.
Supply voltage range must be determined in order. While installing the unit, supply voltage range must be
controlled and appropriate supply voltage must be applied to the unit. Controlling prevents damages in unit
and system and possible accidents as a result of incorrect supply voltage.
There is no power supply switch or fuse on the device. So a power supply switch and a fuse must be added
to the supply voltage input. Power supply switch and fuse must be put to a place where user can reach
easily. Power supply switch must be two poled for seperating phase and neutral. On/Off condition of power
supply switch is very important in electrical connection. On/Off condition of power supply switch must be
signed for preventing the wrong connection.
Temperature Sensor Input
(T C, NTC, PTC, PT-100 or PT-1000)
Supply Voltage
100-240 V (-15%,+10%) 50/60 Hz
230 V (± 15%) 50/60 Hz
115 V (± 15%) 50/60 Hz
24 V (± 15%) 50/60 Hz
24 V (-15%,+10%) 50/60 Hz
10...30 V
Note-2
External
Fuse
(1 A T)
Note-1
Power
Supply
Switch
Note-1:
“ ” “ ”L is (+), N is (-) for 10...30V and
24V Supply Voltage
Note-2: External Fuse is recommended
Note-3: External fuse must be on phase connection in
supply input.
Note-4: External fuse must be on (+) line connection in
supply input.
100-240 V (-15%,+10%) 50/60 Hz
V ( ± %15 ) 50/60 Hz
V ( ± %15 ) 50/60 Hz
24 V ( ± %15 ) 50/60 Hz
24 V ( -%15, +%10 ) 50/60 H z
10...30 V
7
3.2.2 PTC a nd NTC Connection
3.2.1 TC (Thermocouple ) Connection
3.2 Temperature Sensor Input Connection
78
TC
i
i
PTC
Input resistance is greater than 10M .
i
78
Pay attention the cable colours of PTC probe while doing the PTC probe
connection.
i
WHITERED
Connect the wires with the polarity as shown in
the figure left.
Always use compensation wire corresponding
to the thermocouple used. If present, the shield
must be connected to a proper ground.
Input resistance is greater than 10M
.
NTC
78
Input resistance is greater than 10M .
i
78
3.2.3 and PT-1000 ConnectionPT-100
PT-1000
78
PT-100
8
*It is used to decrease the value in the
Set screen and Programming mode
4. Front Panel Definition and Accessin g to the Menus
When power is first applied to the temperature controller, software revision number is shown on
the displays.
4.1 Observation of Software Revision on the Displays
“ ”r RevisionÞSoftware
revision
Number
Operation Screen is shown
If there is an unexpected situation while opening the device, power off the
device and inform a qualified personnel.
c
It is used to increase the
value in the Set screen and
Programming mode
It is used to enter to the SET value
changing mode, programming mode
and used as OK button
Displays Temperature
Value,Temperature Set
Value and Para me ters
Indicates that device is in SET
value changing mode
Blinks in programming
mode
Led indi cation of Output
is active (If blinks, Compressor
protection time is active)
9
4.2 Changing and Saving Temperature Set Value / Alarm Set Value
iIf no operation is performed in Set value mode for 20 seconds, device turns to
operation screen automatically.
11 12
1
3
2
1
2
3
78
TC
NTC, PTC, PT-100, PT1000
4.3 Program Parameters
10
Decimal Seperator Enabling Parameter ( Default = 0 )
Disable.
Enable.
Note : If sensor input type is selected PTC or NTC (BC= 12 or 18) is observed.
Note : When Pnt parameter is changed, change Set, hSt, SuL, SuH, oFt parameters with appropriate values.
Note-6: Supply cables must comply with the requirements
of IEC 60277 or IEC 60245.
Note-5: Stranded cable cross section: 1,5mm²,
Solid cable cross-section: 2,5mm²
The stripping length is 7 to 9 mm.
ESM-1520-N
P
Relay or SSR Driver Output
For SSR Output
(+) (-)
L(+) N(-)
2 3 41 5
5 A@250 V
NOC
a
6
This le d indic ates that alarm
output relay is a ctive
*In the main operation scre en; if
this button pressed,
tempera ture set value will be
displayed. Value can be
changed using increment and
decrement buttons. When Enter
button pre ssed, value is saved
and alarm set value is
displayed. Value can be
changed using increment and
decrement buttons. When Enter
button pressed, alarm set value
is saved and returns back to
main operating screen.
*To access the programming
screen; in the main operati on
screen, pres s this button for 5
seconds
ESM-1520-N
P
ESM-1520-N
P
When SET button is
pressed, SV LED
lights on and
Temperature Set
value is sho wn on the
displays.
Change the Temper ature Set
value with incre ment and
decrement b utto ns.
Press ENTER button
for saving the
Temperature Set
value and to change
the Alarm Set value
SV LED lights off and main
operation screen is shown.
Operation Scre en TEMPERATURE SET Value Screen
TEMPERATURE SET Value Screen ALARM SET Value Screen
SET value is can be adjusted from minimum set value parameter to maximum set value
parameter , Which can be accessed from programming parameters.
ESM-1520-N
P
P
ESM-1520-N
P
ESM-1520-N
P
ESM-1520-N
Change the Alarm Set value with
increment and decrement buttons.
P
ESM-1520-N
ALARM SET Value Screen
P
ESM-1520-N
Operation Scre en
Press ENT ER button
for saving the Alarm
Set value
Operating Ty pe Parameter ( Default = 0 )
Heating
Cooling
Note: If operating type is selected cooling and PID parameters are Device operates with
On-Off control.
parameter skipped.
Temperature Control Selection Parameter On/Off or PID ( Default = 0 )
On - Off selected.
PID selected
Note: If this parameter is select 0, PID parameters will be not observed.If this parameter select 1, Parameter
will be not observed.
Note-1: If this parameter is select the temperature must be lower than temperature set value. If this
condition is not o key
If this parameter is select the temperature
is seen on the main screen for 10 seconds.
must be greater than temperature set value at least
5% of the full s cale. If this condition is not okey is seen on the main sc reen for 10 seconds.
Note-2:
Tune Selection Parameter ( Default = no )
Device does not do Tune operation.
Device does Auto-Tune operation
Device does Self-Tune operation
PID - Proportional Control Parameter ( Default = 10.0 )
This parameter can be ad j usted from %1.0 to %99.9
PID-Integral Parameter( Default = 100 )
This parameter value can be adjusted from 0 to 999
PID-Derivativel Parameter ( Default = 25.0 )
This parameter value can be adjusted from 0.0 to 99.9
PID-Period parameter( Default = 10 )
This parameter value can be adjust from 0 to 150 second.
Operation Scale Min i mum Parameter ( Default = Minimum Value of Device Scal e )
This parameter value can be adjusted from minimum value of device scale to operation scale
maximum parameter
Operation Scale Maximum Para meter ( Default = M aximum Value of Device Sc ale )
This parameter value can be adjusted from operation scale mi nimum par ameter to maximum
value of the device scale.
Hysteresis Parameter for Compressor Output ( Default = 3 )
from 1 to 20°C for NTC (-50°C, 100°C) or PTC (-50°C, 150°C) or J Type TC ( 0°C, 800°C ) or K Type TC
( 0°C, 999°C or PT-100 Type ( -50°C,400°C ) or PT-1000 Type ( -50°C,400°C )
from 0.1 to 10.0°C for NTC(-19.9°C,99.9°C) or PTC (-19.9°C,99.9°C) or PT-100 (-19.9°C,99.9°C) or
PT-1000 (-19.9°C,99.9°C)
In ON/OFF control algorithm, temperature value is tried to keep
equal to set value by opening or closing the last control element.
ON/OFF controlled system, temperature value oscillates
continuously. Temperature value s oscillation period or amplitude’
around set value changes according to controlled system. For
reducing oscillation period of temperature value, a threshold zone
is formed below or around set value and this zone is named
hysteresis. ON
OFF
Temperature
Control
Output
Set
HSt
Time
HSt
Time
Minimum Set Value Parameter ( Default =Minimum value of device scale )
Set value can not be lower than this value. This parameter value can be adjusted from minimum value
of device scale to maximum set value parameter .
Maximum Set Value Parameter ( Default = Maximum value of device scale )
Set value can not be greater than this value. This parameter value can be adjusted from minimum set
value to maximum value of the device scale.
Sensor Offset Parameter ( Default = 0 )
fro m -20 to 20 °C for NTC(-50°C, 100°C) o r PTC(-50°C, 150°C) o r J Type TC (0°C,800°C) or K
Typ e TC (0°C,999°C) or PT-100(-50°C, 400°C)or PT-1000 (-50°C, 400°C) from -10.0 to 10.0°C
for NTC(-19.9°C,99.9°C) or P TC(-19.9°C,99.9°C) or PT-100 (-19.9°C,99.9°C) or PT-1000
(-19.9°C,99.9°C)
Compressor Start Delay at Power On Parameter ( Default = 0)
When power is first applied to the device, compressor is on when this time delay is expired. It can be
adjusted from 0 to 20 minutes.
Compressor Stop-Start Delay Parameter ( Default = 0)
When compressor is inactive, this time delay must be expired for activation of the compressor. It can
be adjusted from 0 to 20 minutes.
Compressor Start-Start Delay Parameter ( Default = 0)
This time delay must be expired between two activation of the compressor. It can be adjusted from 0 to
20 minutes.
Sensor Defe ct Parameter ( Default = 0 )
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to and Time periods in case of
sensor defect.
Compressor is active du ring this time period in case of p robe defect ( Default = 0 )
If probe defect parameter is 2, then this parameter is observed. It can be adjusted from 0 to 99 minutes.
Compressor is active du ring this time period in case of p robe defect ( Default = 0 )
If probe defect parameter is 2, then this parameter is observed. It can be adjusted from 0 to 99 minutes.
Temperature Alarm Function Selection Parameter ( Default =1 )
Alarm function is inactive.
Process Low alarm selected.
Process High alarm selected.
Deviation High alarm selected.
Deviation Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Deviation Range High alarm selected.
Note: If this parameter is select 0, , , , , , and parameters will be not observed.
Temperature Alarm Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum parameter.
Set ( Default =80 )
5 A@ 250 V
Temperature Alarm Parameter
This parameter value can be adjusted form 0.1 to %50 of the device scale if Pnt parameter is 1, 1 to
%50 of the device scale if Pnt parameter is 0.
Hysteresis ( Default =3 )
Programming Section Accessing Password
.
( Default = 0 )
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is selected 0,
password will not be asked
Mode-1 (The increase or decrease in values firstly occurs one by ones, then ten by tens, and
finally hundred by hundreds.
Increment/Decrement M ode ( Default = 0 )Selection Par ame ter
Mode-2 (The rate of increase or decrease of the values accelerates over time.)
i
Temperature Minimum A l arm Para meter ( Default =Minimum Value of Devic e Scale )
If temperature ala rm is active, this parameter value can be adjusted from operation scale minimum
parameter to temperature alarm set maximum p arameter value .
Temperature Alarm Maximum Parameter ( Default = Maximum Value of Device Scale )
If temperature ala rm is active, this parameter value can be adjusted from temperature alarm set
value parameter to operation sca le maximum parameter
Temperature Alarm On Delay Time Parameter( Default = 0 )
Temperature alarm on delay time can be defined with this parameter.
It can be adjusted from 0 to 99 minutes.
Temperature Alarm Off Delay Time Parameter( Default = 0 )
Temperature alarm off delay time can be defined with this parameter.
It can be adjusted from 0 to 99 minutes. If it is higher than 99 is seen on the screen and alarm
latching output is selected. In alarm latching output mode, in order to make passive alarm output,
press DECREMENT button at main screen.
Temperature Alarm DelayAfter Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of temperature
alarm. It can be adjusted from 0 to 99 minutes.
( Default = 0 )
, , , , and Parameters are observed if Operation type is
selected Cooling .“ ”