
5
6
7
188
9
10
AlarmTypeSelectionParameter
Sensor FailureAlarm
Process High Alarm
11
12
2.3PanelMounting
1
2
1-Before mounting the device in your
panel, make sure that the cut-out is of
the right size.
2-Insert the device through the cut-out.
If the mounting clamps are on the unit,
put out them before inserting the unit to
the panel.
2.4InstallationFixingClamp
1
2
The unit is designed for panel mounting.
1-Insert the unit in the panel cut-out from
the front side.
2- Insert the mounting clamps to the
holes that located left and right sides of
the device and make the unit completely
immobile within the panel
2.5RemovingfromthePanel
2
1
Loosen the screws
1-Pull mounting clamps from left and
right fixing sockets.
2-Pull the unit through the front side of
the panel
Before starting to remove the unit
from panel, power off the unit and the
related system.
c
Montage of the unit to a system must be
done with it’s own fixing clamps. Do not
do the montage of the device with
inappropriate fixing clamps. Be sure
that device will not fall while doing the
montage.
c
3. ElectricalWiringDiagram
P/N: ESM-3712-HC
PROCESS
OUT
NC CNO
10A@250V V
1 2 3 4 5 6 7 8 9 10 11 12
(-)
(+)
N L
CATII
Yc
TC
PTC,PT-100
PT-1000
NTC
a
(-)
(+)
CNO
ALARM
OUT
5A@250V V
Process LowAlarm
Deviation HighAlarm
Deviation LowAlarm
Deviation BandAlarm
Deviation RangeAlarm
Alarm Set Value Low Limit Parameter
, minimum process set value parameter to
alarm set value high limit parameter value.
Alarm set value can not be lower than this value.
This parameter value can be adjusted from
Alarm Set Value High Limit Parameter
alarm set value low limit parameter value
to maximum process set value parameter
Alarm set value can not be greater than this value.
This parameter value can be adjusted from
Alarm On Delay Time Parameter
It can be adjusted from 0 to 99 minutes.
Alarm Off Delay Time Parameter
It can be adjusted from 0 to 99 minutes.
When this parameter is 99, if increment button is pressed, is observed and
alarm latching output is selected. To make the alarm latching output passive,
decrement button must be pressed in main operation screen.
Alarm Delay Parameter After Power On
This parameter defines the delay for the alarm is being active after power on. It can
be adjusted from 0 to 99 minutes.
Alarm Set Value Parameter
Alarm output is controlled according to this value.
For alarm type selection paramater = 1 or 2, this parameter value is can be
adjusted from alarm set value low limit parameter to alarm set value high limit
Parameter, for alarm type selection paramater = 3,4,5 or 6 this parameter
value is can be adjusted from 0 to alarm set value high limit Parameter.
Alarm Hysteresis Parameter
Alarm hysteresis value. This parameter is can be adjusted 0 to %50 of the device
scale
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
4.4Easy AccessDiagramOfProgrammingModeParameters
HysteresisParameter
MinimumSetValue
Parameter
PasswordEntering
Screen
MaximumSetValue
Parameter
ProcessOffsetParameter
AlarmTypeSelectionParametresi
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
AlarmSetValueLowLimit
Parameter
AlarmSetValueHigh
LimitParameter
AlarmOnDelayTime
Parameter
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
AlarmOffDelayTime
Parameter
AlarmDelayParameter
AfterPowerOn
AlarmSetValue
Parameter
SET
°C
SV
P
5sec
PasswordEntering
Screen
MainOperationScreen
SET
°C
SV
P
SET
°C
SV
P
ProgrammingMode
EnteringScreen
PressSET/OKbuttonfor
accessingparameters
If no operation is performed in Programming mode for 20 seconds, device turns to
main operation screen automatically
i
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
AlarmHysteresisParameter
OperatingTypeParameter
SwitchOnDelay After
PowerOnParameter
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
CompressorStop/StartTime
DelayParameter
CompressorStart/Start
TimeDelayParameter
ProbeDefect
Parameter
SET
°C
SV
P
SET
°C
SV
P
SET
°C
SV
P
Compressorisactiveduring
thistimeperiodincaseof
Compressorisinactive
duringthistimeperiodin
ProgrammingMode
AccessingPassword
Enterpasswordwithincrementanddecrementbuttons
3.1SupplyVoltageInputConnectionoftheDevice
6
LN
7
Y
c
a
Make sure that the power supply voltage is same indicated on the instrument. Switch on the power supply
only after that all the electrical connection have been completed. Supply voltage range must be determined
in order. While installing the unit, supply voltage range must be controlled and appropriate supply voltage
must be applied to the unit. Controlling prevents damages in unit and system and possible accidents as a
result of incorrect supply voltage.
There is no power supply switch or fuse on the device. So a power supply switch and a fuse must be added
to the supply voltage input. Power supply switch and fuse must be put to a place where user can reach
easily. Power supply switch must be two poled for seperating phase and neutral. On/Off condition of power
supply switch is very important in electrical connection. On/Off condition of power supply switch must be
signed for preventing the wrong connection.
External fuse must be on phase connection in supply input.
External fuse must be on (+) line connection in supply input.
V
Z
Note-3
Note-2
100...240V (-%15;+%10)50/60Hz2VA orV
24V (-%15;+%10)50/60Hz2VA orV
24V (-%15;+%10)2WZ
Note-1
The instrument is protected with an internal fuse (Please refer to Note-1 for information). In
case of failure it is suggested to return the instrument to the manufacturer for repair.
c
Note-2: “L” is (+), “N” is (-) for 24V Supply
Voltage
Z
SupplyVoltage
Power
Supply
Switch
External
Fuse
(1 A T)
Note-3: External Fuse is recommended
Note-1:Thereisaninternal33R fusible
flameproofresistorin
Thereisaninternal4R7 fusibleflameproof
resistorin
W
W
100-240V 50/60Hz
24V 50/60Hz
V
W
100...240V (-%15;+%10)50/60Hz2VAV
24V (-%15;+%10)50/60Hz2VAV
24V (-%15;+%10)2WZ
SupplyVoltageInput
RelayorSSR
DriverOutput
ForSSrOutput
TemperatureSensorInput
(TC,NTC,PTC,PT-100or
PT-1000)
3.2.2PTCandNTCConnection
3.2.1TC(Thermocouple)Connection
3.2TemperatureSensorInputConnection
1211
TC
i
i
10
PTC
Input resistance is greater than 10M .W
i
1211
10
Pay attention the cable colours of PTC probe while doing the PTC probe
connection.
i
WHITERED
Connect the wires with the polarity as shown in
the figure left.
Always use compensation wire corresponding
to the thermocouple used. If present, the shield
must be connected to a proper ground.
Input resistance is greater than 10M W.
NTC
1211
10
Input resistance is greater than 10M .W
i
1211
10
3.2.3 andPT-1000ConnectionPT-100
PT-1000
1211
10
PT-100
Displays
Temperature
Value,
TemperatureSet
Value
andParameters
Itisusedtoenterto
theSETvalue
changingmode,
programmingmode
andusedasOK
button.
Itisusedto
increasethevalue
andaccesstothe
parameterin
programming
mode.
Decrement
Button
Ledindicationof
ProgrammingModeisactive
Note-1
Note-1: If increment or decrement button is pressed for 5 seconds continuously, increment and
decrement number become 10, if increment or decrement button is pressed for 10 seconds
continuously, increment and decrement number become 100.
4.FrontPanelDefinitionand AccessingtotheMenus
TemperatureController
ESM-3712-HC
SET
°C
SV
P
Ledindicationof
Outputisactive
(Ifblinks,Compressor
protectiontimeisactive)
LedindicationofSETvalue
changingmode
When power is first applied to the temperature controller, software revision number is shown on
the displays.
4.1ObservationofSoftwareRevisionontheDisplays
TemperatureController
ESM-3712-HC
SET
°C
SV
P
TemperatureController
ESM-3712-HC
SET
°C
SV
P
“r” RevisionÞ
Revision
Number
MainOperationScreenisshown
If there is an unexpected situation while opening the device, power off the
device and inform a qualified personnel.
c
Note-1
Ledindicationof
Alarm
ActiveLed
4.2ChangingandSavingSetValue
SET
°C
SV
P
WhenSET buttonispressed,SVLED
lightsonandSET valueisshownon
thedisplays.
SET
°C
SV
P
SETValueScreen
ChangetheSET valuewith
incrementanddecrement
buttons.
SET
°C
SV
P
PressSET buttonforsavingthe
SET value
SVLEDlightsoffandmainoperation
screenisshown.
SET
°C
SV
P
MainOperationScreen
SETValueScreen
i
If no operation is performed in Set value mode for 20 seconds, device turns to main
operation screen automatically.
SET value is can be adjusted from minimum set value parameter to maximum set value
parameter , Which can be accessed from programming parameters.
MainOperationScreen
4.3ProgramParameters
i
, , , , and parameters are observed if
Operating type is selected “ Cooling ”. If operating type is selected “ Heating ”
beginning of the parameters list is shown.
Hysteresis Parameter for Output ( Default = 1 )
1 to 100 °C for TC Type Devices,
1 to 100 °C for PT-100 (-50°C, 400°C) and PT-1000 (-50°C, 400°C),
0.1 to 10.0 °C for PT-100 (-19.9°C, 99.9°C) and PT-1000 (-19.9°C, 99.9°C),
1 to 20 °C for PTC (-50°C, 150°C) and NTC (-50°C, 100°C),
0.1 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
Minimum Set Value Parameter ( Default =Minimum value of device scale )
Set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum set value parameter
Maximum Set Value Parameter ( Default = Maximum value of device scale )
Set value can not be greater than this value. This parameter value can be adjusted
from minimum set value to maximum value of the device scale
ProcessOffsetParameter(Default=0)
-100 to 100 °C for TC Type Devices,
-100 to 100 °C for PT-100 (-50°C , 400°C) and PT-1000 (-50°C , 400°C),
-10.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C) and PT-1000 (-19.9°C, 99.9°C),
-20 to 20 °C for PTC (-50°C, 150°C) and NTC (-50°C, 100°C),
-10.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
SwitchOnDelay AfterPowerOnParameter
When power is first applied to the device, this time delay must be expired for
activation of the compressor. It can be adjusted from 0 to 20 minutes
Compressor Stop/Start Time Delay Parameter
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
ProbeDefectParameter
Compressorisactiveduringthistimeperiodincaseofprobedefect
IfProbeDefectParameteris,thenthisparametercanbe
observed.Itcanbeadjustedfrom0to99.
Compressor is OFF in case of probe defect
Compressor is ON in case of probe defect
Compressor operates periodically according to and time
periods in case of probe defect.
Compressor Start/Start Time Delay Parameter
This time delay must be expired between two activation of the compressor.
It can be adjusted from 0 to 20 minutes.
OperatingTypeParameter
Heating
Cooling
Compressorisinactiveduringthistimeperiodincaseofprobedefect
IfProbeDefectParameteris,thenthisparametercanbe
observed.Itcanbeadjustedfrom0to99.
Programming Mode Accessing Password
It is used for accessing to the programming mode. It can be adjusted from 0 to 999.
If it is selected 0, password is not entered for accessing to the parameters.
Max.24mA,Max.16V Z