Honeywell T6360 Manual


Læs gratis den danske manual til Honeywell T6360 (11 sider) i kategorien Termostat. Denne vejledning er vurderet som hjælpsom af 51 personer og har en gennemsnitlig bedømmelse på 4.7 stjerner ud af 26 anmeldelser. Har du et spørgsmål om Honeywell T6360, eller vil du spørge andre brugere om produktet?

Side 1/11
EN0R8281 R3 2003
T4360/T6360
LINE VOLTAGE
ROOM THERMOSTATS
PRODUCT SPECIFICATION SHEET
The T4360/T6360 range of thermostats
are designed to provide automatic
ON/OFF control for gas valves,
circulation pumps, relays and zone
valves in all heating, cooling, or
heating/cooling installations where
single or changeover switching up to
10 A (resistive load) or 3 A (inductive
load) is required.
In addition a 16 A (resistive load)
variant is available for direct switching
of high current carrying loads.
Nine models of the thermostat are
available, in a wide range of feature
combinations.
FEATURES
Dual diaphragm sensing element ensures close
temperature control for all loads and applications
Attractive modern styling makes this thermostat ideal
for locating in the living space
Available with or without heat anticipation to suit the
application
The T6360 has changeover contacts for use in
cooling or heating/cooling applications
Versions with switches for positive-off selection, or
summer/ winter (heat/cool) changeover operation
Mounts directly onto wall or conduit box
Improved eas
y
-to-wire terminals with built-in
conductor clamps to ensure wiring is retained
securely
Double insulated. No earth wire required for
operation. Earth "parking" terminal available on
selected models
Optional extras available are:
range stops F42006646-001
tamperproof cover F42007110-001 (opaque) or
F42007110-002 (transparent)
additional wallplate for special mounting
requirements F42007789-001
T4360/T6360 LINE VOLTAGE ROOM THERMOSTATS
EN0R8281 R3 2003 2
SPECIFICATIONS
MODEL HEAT
ANTICIPATOR
CHANGEOVER
CONTACTS
INDICATOR
LAMP
SUMMER/
WINTER
SWITCH
ON/OFF
SWITCH
16 AMP
RATING
FROST
PROTECT
FUNCTION
TAMPER-
PROOF COVER
NIGHT
SETBACK
HEATER
SPECIAL
ANTICIPATOR
T4360A
T4360B
T4360C
T4360D
T4360E
T4360F
T6360A
T6360B
T6360C
Versions available with or without this feature
For thermal actuator control
DIMENSIONS
Switch type : T4360 S.P.S.T. (Heating)
T6360 S.P.D.T. (Heating/Cooling)
Electrical ratings : 230Vac, +/-10%, 50…60Hz
T6360A,B,C 10(3) A Terminal 3 (Heat),
6(2) A Terminal 4 (Cool)
T4360A,C,E 10(3) A Terminal 3
(Heating)
T4360B 16 A Terminal 3 (Heating)
T4360D 6(2) A Terminal 2 (Heating
or Cooling)
T4360F 2(2) A Terminal 3 (Heating)
Manual switches on T4360C,D and
T6360C rated 10(3) A
Temperature
setting range
: 10 to 30oC
(0 to 20oC - T4360A only)
Terminals : Terminals sized to accept up to 2 x
single or multi-stranded wires from
1.0 mm2
to 2.5 mm2.
16 A version will accept one 4.0 mm2
wire per terminal.
Lamp terminals suitable for only one
wire per terminal up to 2.5 mm2max.
Each terminal has a conductor clamp
for securing the wiring conductor and is
suitable for both blade and cross-head
screwdrivers.
Earth "parking" terminal to comply with
IEC guidelines.
Performance : Maximum differential 1.0oC at 20oC at
heat ramps of 3oC per hour, with
anticipator connected.
Typical differential 0.5oC.
Switch life : Greater than 100,000 operations (all
loads) for main switch.
10,000 operations for auxiliary on/off or
heat/cool switches.
Environmental
requirements
: Operating temperature range 0 to 40oC
Shipping and storage range -20 to 50oC
Humidity range 0 to 90% R.H. (non-
condensing)
Approvals : CE mark, complying with standards
EN60730-1 (1995), EN55014-1 (1997),
EN55014-2 (1996).
Product must be wired as shown for CE
compliance.


Produkt Specifikationer

Mærke: Honeywell
Kategori: Termostat
Model: T6360

Har du brug for hjælp?

Hvis du har brug for hjælp til Honeywell T6360 stil et spørgsmål nedenfor, og andre brugere vil svare dig