Intermatic ET1125C Manual


Læs gratis den danske manual til Intermatic ET1125C (3 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 4 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 2.5 anmeldelser. Har du et spørgsmål om Intermatic ET1125C, eller vil du spørge andre brugere om produktet?

Side 1/3
Slide down
to remove
battery case
Snap out catch
Tilt top forward
Electronic 24-Hour
Time Switch
Time Switch
Input Voltage: 120/208/240/277 VAC, 60 Hz
Contact Conguration: SPST (ET1105C), DPST (ET1125C). See
wiring diagrams on next page.
Switch Ratings—ET1105C, ET1125C (per pole)
30 A Inductive/Resistive, 120/240 VAC, 60 Hz
20 A Magnetic Ballast, 120-277 VAC, 60 Hz
1 A Electronic Ballast 120-277 VAC, 60 Hz
20 A Resistive, 28 VDC
5 A Tungsten: 120/240 VAC, 60 Hz
1 HP, 120 VAC, 60 Hz
2 HP, 240 VAC, 60 Hz
Set Points (Events)—Each load output of the Time Switch can sup-
port up to 14 timed ON and 14 timed OFF events per day.
Battery-Powered Clock Operation—3 years minimum (uses 2 AAA
industrial grade alkaline batteries, supplied)
Minimum ON or OFF time—1 minute
Maximum ON or OFF time—23 hours, 59 minutes
Shipping Weight—2.5 lb. (1.1 kg)
Installation and User Instructions
MODEL ET1100 Series
The Intermatic ET1100 Series Electronic 24-Hour Time Switch
automatically switches loads to a preset daily schedule with to-the-
minute accuracy.
Use the ET1100 series as an ON/OFF timer in applications requiring
24-hour load control such as lighting, air conditioning systems, pumps,
etc. Each load output of the Time Switch can support up to 14 timed
ON and 14 timed OFF events per day. The program can be overridden
by pushing the ON/OFF load override button(s).
The ET1100 Series Time Switch is designed to directly switch tungsten
or ballast loads up to its rating, and inductive or resistive loads up to
30 A at 120, 208, 240, or 277 VAC.
Specifications
With Battery
Carryover
Description
Installation Instructions
Front View
Rear View
B
A
WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
Installation and/or wiring must be in accordance with national and local electrical code
requirements.
For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of
the UL514B (standard for fitting conduit and outlet boxes) are to be used.
This enclosure does not provide grounding between conduit connections. When metallic conduit
is used, you must also install grounding type bushings and jumper wire.
For plastic enclosures, bonding between conduit connections is not automatic and must be
provided as part of the installation.
• Use #18 - #10 AWG wires, rated at least 75°C - COPPER conductors ONLY.
If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent
unexpected application power.
Make sure there is no wire insulation under the terminal plate on the time switch connector.
Firmly tighten terminal screws.
• Do not remove insulator that is covering terminals.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
Do NOT touch circuit board components, contact can create a static discharge, which can
damage the microprocessor.
1. Remove the mechanism
from the case by
depressing the catch at
the top of the case and
pulling out, as shown.
3. The timer is shipped with DST (Daylight Saving
Time) enabled. To disable DST, insert a jumper
at location marked DST. See location in Rear B
View above and detail at the right.
4. ET1125C ONLY—Decide whether you want
to control multiple loads simultaneously (SIM),
independently (IND), or with a 2-second pulse
(PUL) (e.g., for use with mechanically held
contactors or bell ringing applications), and
make sure the jumper is positioned accordingly.
See location in Rear View above and detail B
at the right. (The unit is shipped with the loads
set for IND.)
EnclosuresET11x5C – TYPE 1 indoor metal enclosure
KnockoutsCombination 1/2-3/4 inch size, 1 on back and each side,
2 on bottom
Wire SizeAWG #18 through #10
2. Set voltage selector for desired input voltage.
The timer is shipped with voltage set for 277
VAC. To operate at 120, 208 or 240 VAC, move
the selector switch to the desired setting as
marked on the circuit board. See location in A
Rear View above and detail at the right.
1
Knockouts
Mounting holes
1
Neutral
120 VAC
Input
Hot
2 3 4
Timer Power
Load
Only install jumper
if timer input
and load voltage
are the same
ET1105 configured for SPST, 120 VAC load
1
Line 2
240VAC Input
Line 1
2 3 4 5 6
Line 1
Line 2
Install jumper only if timer input
and load voltage are the same
Timer Power
Load
ET1125 configured for 240VAC DPST load
with jumper set to SIM
1
L2/N
120/208/240/277
VAC Input
Line 1
2 3 4 5 6
ON
Install jumper only if timer input
and load voltage are the same
OFF
Timer Power
with jumper set to PUL
1
L2/N
120/208/240/277
VAC Input
Line 1
2 3 4 5 6
Timer Power
Load
1
Load
2
Line
1
Line
2
ET1125 configured for 2 SPST loads
with jumper set to IND
1
L2/N
120/208/240/277
VAC Input
Line 1
2 3 4 5 6
Timer Power
Load
1
Load
2
Line
1
Line
2
ET1125 configured for DPST loads
with jumper set to SIM
Programming Overview
By pressing the button, the Time Switch will cycle through the MODE
menus necessary for programming the current time, date, and timed
events.
The basic procedure is to use the button to move from one MODE
menu to the next (e.g., DATE, TIME, etc.), the or buttons for the +
rst part of a setting (e.g., MONTH), the button to move to the ENTER
next part of the setting (e.g., YEAR), then to exit and move to MODE
the next menu. To skip a menu, press to move ahead.MODE
If you make a mistake, press the button repeatedly to MODE
cycle back around to the error, then make the correct entry.
NOTE: DATE and TIME must be set before you can access any
other programming menus.
Setting Date
1. Press the MODE button repeatedly until the words SET and
DATE appear in the upper area of the display.
2. Press the or buttons to enter the current Month.+
3. Press the ENTER button when the Month is correct to save the
setting. The screen advances to current Date.
4. Again press the + or buttons to enter the current Date,
followed by the button.ENTER
5. Repeat to set the correct Year.
6. Press the MODE button to exit and advance to setting the time.
Wiring Diagrams
9. Insert the wire ends under the proper terminal plates (see
wiring diagrams elsewhere on this page) and tighten the
screws rmly.
10. Connect ground wire to grounding terminal at bottom of enclosure.
11. Replace the plastic insulator on the retaining post.
12. Remove the battery case by sliding it down as shown by the
arrows, then install 2 AAA alkaline batteries. Make sure the
batteries are pointing in the direction shown.
13. Verify that the display is to make sure the batteries are OK.ON
If the display shows scrambled information, press the RESET
button to clear it up.
14. Apply power to the Time Switch.
IMPORTANT: ENTER Press and hold the button, then press the
RESET button. The screen will ash 12:00 AM, and timer status
is Manual Mode.
NOTE: You must reset the time switch using this procedure
whenever you change the jumpers.
The Time Switch is now ready for programming.
5. Mount the enclosure in the desired location using the 3 mounting
holes provided.
Position at eye level if possible, providing space to the left of the
enclosure for the cover to swing open fully, as shown.
6. Replace the mechanism in the enclosure.
7. Lift the left side of the plastic insulator off the retaining post and
pivot it up and away to expose the terminal strip.
8. Strip the supply and load wires to 1/2”. Use #18 -
#10 AWG wires, rated at least 75°C - COPPER
conductors ONLY.
2