Intermatic GM40AV Manual


Læs gratis den danske manual til Intermatic GM40AV (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 9 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 5 anmeldelser. Har du et spørgsmål om Intermatic GM40AV, eller vil du spørge andre brugere om produktet?

Side 1/4
MANUAL OVERRIDE OPERATION
With the manual switch in the middle position, the GM40AV is in
automatic mode and will switch at the programmed times.
In the upper position “I”, the load is continuously ON.
In the lower position, “O”, the load is continuously OFF.
TRIPPERS IN
Green Status LED: OFF
(Normally-open contacts open)
TRIPPERS OUT
(Normally-open contacts closed)
Figure 3
Rotate timer dial clockwise only.
Jumper wires are not included.
Alterations or modifications to the device will void warranty
GM40AV Series General Purpose Electromechanical Commercial Time Switches
Installation & Operating Instructions
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
More than one circuit breaker or disconnect switch may be required to de-energize the equipment before
servicing.
Do not use the manual shut-off position of the timer for equipment servicing. Always disconnect the power
at the circuit breaker(s) or disconnect switch(es).
Installation and/or wiring must be in accordance with national and local electrical code requirements.
This Time Switch is designed to control one or two single phase loads. Do not use to directly control three
phase loads. Consult a qualified electrician if you are required to control three phase equipment.
Some terminals in the Time Switch may be energized even if the yellow and green LED indicators are OFF.
The circuit conductors shall have an ampacity not less than the maximum total load to be controlled.
For all connections, use COPPER conductors ONLY – min. #8 AWG wires for 40 A loads, or #10 AWG wires
for 30 A loads, min. 90°C (194°F)
Over current protection shall have an interrupting rating sufficient for the application control circuit voltage
and the total load current of the equipment being controlled.
A fuse or circuit breaker shall be connected in series with each ungrounded conductor (and shall be able to
simultaneously open each conductor.
Check all terminals and wires with an appropriate voltage meter before touching.
This enclosure does not provide grounding between conduit connections. When metallic conduit is used,
you must also install grounding type bushings and jumper wire, in accordance with the (NEC) National
Electrical Code requirements.
For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the
UL514B (standard for fitting conduit and outlet boxes) are to be used.
Replace plastic insulator covering terminals before powering ON.
WARNING
Read Instructions completely before installation and retain this booklet for future reference.
INSTALLATION INSTRUCTIONS
1. Open door and remove the interior protective cover by releasing the spring latch. (See Figure 1)
2. Remove the printed circuit board by releasing the spring latch holding the bottom of the board.
(see Figure 1)
3. Select knockouts to be used. Remove the inner 1/2" knockout by inserting a athead screwdriver
in the slot and carefully punch the knockout loose. Remove slug. If 3/4" knockout is required,
remove the outer ring with pliers after removing the 1/2" knockout. Smooth edge with knife, if
necessary.
4. Place the enclosure in the desired mounting location, and mark the three mounting holes (refer to
Figure 2 for dimensions). Install the top screw rst with one of the supplied spacers, and then hang
the enclosure by the keyhole. Drive the remaining two screws at the bottom of the enclosure
through the mounting holes while passing each screw through one of the supplied spacers and in
to the wall.
5. Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs
into enclosure, carefully tighten hub lock nut. Do not over-torque.
6. Replace printed circuit board making sure to engage spring latch at the bottom of PCB.
7. Wire in accordance with national and local electrical and safety codes (see wiring diagrams).
8. Grounding: Terminate all ground wires to the ground lug inside the case at the bottom of the
enclosure.
9. Replace interior protective cover.
10. Close the enclosure door.
PROGRAMMING INSTRUCTIONS
SETTING THE CLOCK TIME
Rotate the program dial gradually clockwise until the time of day on the outer dial is nearly aligned with
the triangle marker at the 2 o’clock position. Then set time to the minute by rotating minute hand
clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on
the inner dial.
SETTING ON/OFF TIMES
Move the white tab (tripper) on the outer dial outward at the start of the desired ON period. Move each
adjacent tab outward until the desired OFF time is reached. (See Fig. 3)
Figure 2 - Rear View of Enclosure
with mounting hole dimensions
6-1/8
2-1/2
Figure 1 - PCB Latch
Interior
Protective
Cover
Timer Mechanism
Spring Latch
GM40AV SERIES TERMINAL DESIGNATIONS
NO 2NC 2NONCL 2/NL 1
T
TIMER
L N
COM
LOAD
#1
LOAD
#2
COM2
120/277 VAC Application Two Loads
COM2NO 2NC 2NONCL 2/NL 1
T
TIMER
L1 L2
COM
LOAD
#1
208/240 VAC Application One Load
NO Contacts:
40 A Resistive, 120-277 VAC
30 A Ballast, 120 VAC
20 A Ballast, 277 VAC
15 A Tungsten, 120 VAC
300 VA Pilot Duty, 120-240 VAC
1 HP, 16 FLA, 90 LRA @ 120 VAC
2 HP, 12 FLA, 52 LR A @ 208-277 VAC
NC Contacts:
30 A Resistive, 120-277 VAC
10 A Ballast, 277 VAC
2 A Tungsten, 120 VAC
1 HP, 12 FLA, 30 LRA @ 120 VAC
2 HP, 10 FLA, 30 LRA @ 240 VAC
WIRING CONNECTIONS:
Screw box lug terminals
ENVIRONMENTAL RATINGS:
Operating Temperature Range:
-40° F to 131° F (-40° C to 55° C) Non “Q” Models
-4° F to 131° F (-20° C to 55° C) “Q” Models
Operating Humidity:
10-95% RH, non-condensing
ENCLOSURE DIMENSIONS:
8.795" H x 6.631" W x 2.935" D
SHIPPING WEIGHT:
2 lbs.
ELECTRICAL RATINGS
Risk of Fire or Electric Shock
NOTICE


Produkt Specifikationer

Mærke: Intermatic
Kategori: Ikke kategoriseret
Model: GM40AV

Har du brug for hjælp?

Hvis du har brug for hjælp til Intermatic GM40AV stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Intermatic Manualer

Intermatic

Intermatic EK4536 Manual

12 November 2025
Intermatic

Intermatic LC4521C Manual

11 November 2025
Intermatic

Intermatic OP2GY24 Manual

8 November 2025
Intermatic

Intermatic OP2BK24 Manual

6 November 2025
Intermatic

Intermatic WP1250MXD Manual

5 November 2025
Intermatic

Intermatic OP2BK18 Manual

4 November 2025
Intermatic

Intermatic WP1030MXD Manual

4 November 2025
Intermatic

Intermatic OP5BK24 Manual

4 November 2025
Intermatic

Intermatic OP5GY24 Manual

4 November 2025

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

Topping

Topping DX5 Manual

4 December 2025
CyberPower

CyberPower GX150C2 Manual

4 December 2025
SPT

SPT SM-1024K Manual

4 December 2025
Novy

Novy 990037 Manual

4 December 2025
D&R

D&R Hybrid-2 Manual

4 December 2025
Iogear

Iogear GHDSW4K3 Manual

4 December 2025
Vevor

Vevor WK320016-1 Manual

4 December 2025
ELO

ELO E426554 Manual

4 December 2025