KNX Sensor and Transformer
Ref.-no.: WS 10 W, WS 10 HT, WS 10 R
Operating Instructions
Wind Sensor with Heating
Heating Transformer
Rain Sensor
c
1. Safety instructions
Attention: Electrical equipment must be installed and fitted by
qualified electricians only.
2. Wind Sensor Function
Wind sensor c serves for detecting and evaluating the wind velocity and
is provided for outdoor installation. It can be installed by means of the
attached mounting bracket.
Via a reed contact, the rotating speed is detected and converted into an
analogue output signal (0 ... 10 V).
An integrated heating (heating transformer option required) facilitates
operation during frost periods.
2.1. Wind Sensor Connection
Where:
1: white reference potential (earth)
2: brown 24 V DC operating voltage
3: green 0 .. 10 V + output
4: yellow 0 .. 10 V - output (earth)
5 + 6: grey / pink 24 V AC/DC heating transformer supply
Stand: Aug-08 325 061 13
KNX Sensor and Transformer
Ref.-no.: WS 10 W, WS 10 HT, WS 10 R
3. Rain Sensor Function
Rain sensor serves for detecting and evaluating the precipitation and
is provided for outdoor installation. It can be installed by means of the
attached 11 mounting bracket.
Via a meander and by utilising the conductivity of water, wetting by
precipitation is detected, evaluated and converted into an output signal
(dry = 0 V, rain = 10 V).
Intermediate values are not detected.
The output signal is reset only after the sensor surface has dried and
when an OFFdelay of 4 minutes has elapsed. The integrated heating
(additional heating transformer required as an accessory) accelerates the
drying process and melts ice and snow.
3.1. Rain Sensor Connection
Where:
1: white reference potential (earth)
2: brown 24 V DC operating voltage
3: green 0 .. 10 V + output
4 + 5: yellow/grey 24 V AC/DC heating transformer supply
4. Installation Instructions
To supply the sensors (24 V DC) and to evaluate the sensor signals
an additional electronic device (e. g. the instabus weather station) is
required that can send measured value or command telegrams to the
instabus EIB, depending upon the analogue signals.
Install the sensors in an accessible place to facilitate possibly
necessary cleaning.
Do not install sensors in the vicinity of transmitting equipment (e. g.
mobile radio converters).
Do not install sensor lines in parallel with lines carrying mains voltage
or loads.
To avoid electromagnetic irradiation keep a distance of a few
centimetres from such lines.
Note additionally for the wind sensor:
Ensure correct positioning of the sensor (e. g. position not sheltered
from the wind).
Note additionally for the rain sensor:
Do not damage the sensing surface and wipe with a mild cleaning
agent at a regular intervals.
When installing the sensor, ensure unobstructed exposure to rain (do
not install under eaves).
2


Produkt Specifikationer

Mærke: JUNG
Kategori: Ikke kategoriseret
Model: WS10H

Har du brug for hjælp?

Hvis du har brug for hjælp til JUNG WS10H stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret JUNG Manualer

JUNG

JUNG 1710DE Manual

3 Juni 2025
JUNG

JUNG MALS1133 Manual

31 December 2025
JUNG

JUNG MAAL1133 Manual

14 December 2024
JUNG

JUNG MAGO1193 Manual

10 December 2024
JUNG

JUNG MAA1193 Manual

10 December 2024
JUNG

JUNG MACD1193WW Manual

10 December 2024
JUNG

JUNG WS10D Manual

10 December 2024
JUNG

JUNG AL1561.07F Manual

10 December 2024
JUNG

JUNG 1745DSTE Manual

10 December 2024
JUNG

JUNG MALS1193 Manual

10 December 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer