Dimming Module with 0 –10 V-
Part of the Vive Family
Start Here
Lutron, Pico, PowPak, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license.
Google is a registered trademark and Android and Chrome are trademarks of Google Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2013 – 2018 Lutron Electronics Co., Inc.
A On PowPak Dimming Module
with 0 –10 V , hold -Toggle
button “ u” for 6 seconds until
lights flash.
The Load Status LED will begin
flashing twice per second.
Associate Wireless Transmitters to
PowPak Dimming Module with 0 –10 V-
Before beginning this step, make sure that there are no
other PowPak modules being set up within the same
building. It is possible that wireless transmitters from other
systems can be incorrectly associated to this module.
1
C On PowPak Dimming Module with 0 –10 V , hold -
Toggle button “ u” for 6 seconds to save association.
Lights will flash and LED will quickly blink for
2seconds.
B Hold the indicated button on each transmitter for
6seconds. Lights will flash to show that wireless
transmitters have been associated.
Test
Link
D Permanently install wireless transmitters
(consult individual component installation guides for
information).
Low-End Trim
A
Enter low-end trim adjustment mode:
Press and hold the button “Lower
Ǻ
” on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing.
B
Adjust the low-end trim:
Use the Raise button “ŷ
” and button “Lower
Ǻ
” on the fixture control to adjust and set the
lights to the desired low-end (1 to 45%).
C
Save the low-end trim:
Press and hold the Toggle button “ u” for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A
Enter high-end trim adjustment mode:
Press and hold the button “Raise ŷ
” on the fixture control for 12seconds.
The lights will flash and the load status LED will flash.
B
Adjust the high-end trim:
Use the Raise button “ŷ
” and button “Lower
Ǻ
” on the fixture control to adjust and set the
lights to the desired high-end (55 to 100%).
C
Save the high-end trim:
Press and hold the Toggle button “ u” for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before
performing the following procedures.
Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim
may need to be adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out if
trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any
abnormal operation.
• The factory default high-end trim is suitable for most applications but can be
adjusted as desired.
4
5Set Minimum Light Level (Optional)
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas, activate Minimum Light Level
mode.
A
Enter minimum light level adjustment mode:
Press and hold Toggle button “ u” and button “Lower
Ǻ
” for 12 seconds. Lights will flash high-low-high and LED will begin
flashing.
If lights stop flashing and go to high-end, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
B
Change the minimum light level:
Press button “Raise ŷ
” to set minimum light level to low-end.
Press button “Lower
Ǻ
” to set minimum light level to OFF.
C
Save the minimum light level:
Press and hold Toggle button “ u” for 6seconds. LED will quickly flash to indicate that new level has been saved.
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
For FCC/IC information: Please visit: www.lutron.com/fcc-ic
Calibrate the Radio Powr Savr Daylight Sensor
Daylight Sensor will control all wired fixtures equally.
A
Press and release the “Cal.” button on the Daylight Sensor.
B
Set lights in room to desired light level.
C
Press and hold the “Cal.” button for 6seconds.
D
Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Dimming Module with 0 –10 V must be -
used. For detailed setup refer to the tuning section of the Radio Powr Savr Daylight Sensor
installation guide.
• Select the PowPak Dimming Module with 0 –10 V that you want to adjust by pressing the -
toggle button.
Test
Link
2
Raise Lower
Favorite
Set a Favorite Light Level (Optional)
For Pico remote controls with a button.Favorite
A
Adjust lights to desired level:
Use the button “Raise ” or Lower button “ ” on the Pico
remote control.
B
Save favorite level:
Press and hold the button for 6seconds. The load will Favorite
flash 3 times to confirm that the Favorite level is saved.
3
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the
PowPak Dimming Module with 0 –10 V and connected -
devices back to factory default settings. Before beginning,
make sure that all devices are connected and powered.
A
Triple-tap the Toggle button “ u” on the PowPak Dimming
Module with 0 –10 V and hold until the LED begins to flash -
slowly; release button.
B
Within 3 seconds of the start of flashing, triple-tap the same
button again and the LEDs will flash rapidly indicating that the
unit has been reset to factory defaults.
Note: Any associations or programming previously set
up with the PowPak will be erased and will need to be
re-programmed.
Customer Assistance:
U.S.A. / Canada: 1.844.LUTRON1
United Kingdom: 0800.282.107
Europe: +44.(0)20.7680.4481
Mexico: +1.888.235.2910
China: 800.901.849
Central / S. America: +1.610.282.6701
Other Countries: +1.610.282.3800
www.lutron.com/support
6Set Occupancy Light Levels (Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
A
Set desired occupancy light levels:
Use / buttons “Raise Lower ŷ
/
Ǻ
” on the PowPak Dimming Module with 0 –10 V or / / -Raise Lower buttons “ ” on all
associated Pico Remote Controls.
B
Save occupancy light levels:
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor without a Lights On
button. Release when Sensor lens starts to flash.
Or, press and hold button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor. Release when Lights On
Sensor lens starts to flash.
Ballasts cannot be controlled
locally from PowPak Dimming
Module with 0 –10 V .-
• Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V are energized.-
• Ensure that the PowPak Dimming Module with 0 –10 V switched hot lead is wired to the lighting fixture(s).-
• Ensure that the PowPak Dimming Module with 0 –10 V control lines are wired to the lighting fixture(s).-
Reset to factory defaults.
Lights do not dim as expected. • Ensure that 0 –10 V control lines are wired properly.-
• Ensure that fixture does not require an inverted signal (10 – 0 V control).-
Lights do not respond to Wireless
Transmitter(s).
• Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V and ballasts are energized.-
• Ensure that Wireless Transmitters are associated to the PowPak Dimming Module with 0 –10 V-.
Reset to factory defaults.
Lights are unstable at low-end or
flash/flicker at turn-on or turn-off. • Adjust low-end trim.
Wireless Transmitter(s) cannot be
associated to PowPak Dimming
Module with 0 –10 V .-
• The maximum number of Wireless Transmitters have been associated to the PowPak Dimming Module with
0 –10 V-. To remove a previously set up Wireless Transmitter, tap a Wireless Transmitter button three times; on
the third tap hold for three seconds and then tap three more times.
PowPak is in emergency mode
(RMJS-8T-DV-B-EM only).
• In systems with a Vive hub: Contact Lutron Customer Assistance for further details.
• In systems without a Vive hub: Wait 90 minutes for the PowPak to return to normal operation.
PowPak will not go into
emergency mode
(RMJS-8T-DV-B-EM only).
• Contact Lutron Customer Assistance for further details.
Troubleshooting www.lutron.com/support