Installaon Manual
Type:
:
:
::DRA DIN rail power supply Series DRA-40, DRA-
(
(
(
(( :
:
:
:: 60)
)
)
))
DRA- - INPUT: -240VAC 0.8A 50/60Hz OUTPUT: V 3.34A 40 12 100 12
DRA- - INPUT: -240VAC 0.8A 50/60Hz OUTPUT: V 1.7A 40 24 100 24
DRA- - INPUT: -240VAC 1.3A 50/60Hz OUTPUT: V 5A 60 12 100 12
DRA- - INPUT: -240V 1.3A 50/60Hz OUTPUT: V 2.5A 60 24 100 AC 24
Introducon
DRA is a DIN rail power supply series featuring adjustable output current. Users are able to set its output current to
a range of 10% - 100% of rated current via 1-10Vdc, PWM signal or resistance. Like other Mean Well s DIN series, ’
they can be mounted on a TS35 Standard DIN rail.
Installaon
( )1 Always allow good venlaon clearances, 5mm le and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheang. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
( )2 The appropriate mounng orientaon for the unit is vercal, the input terminals the bottom and output on at
the top. Mounng orientaons other than that, such as upside down, horizontal, or table-top mounng, is not
allowed.
( )3 Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
7
10
15
20
Cross-secon of
Lead(mm2 )
0.8
1.3
2.1
3.3
Note Current each wire carries should be de-rated to 80% of the current suggested :
above when using 4-6 wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connecon and the screw terminals are
securely xed to prevent poor contact. If the power supply possesses mul-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
( )4 Use wires that can withstand temperatures of at least 80°C, such as UL1007.
( )5 Recommended wire strapping length m (0.197 . is 5m ”)
( )6 Recommended screwdriver is 3 , sloed type.mm
( )7 The recommended torque seng for terminals(TB1) is 5 kgf‐cm (4.4 Lb‐in),
terminals(TB2) is 5 5 .8 kgf‐cm ( Lb‐in).
( )8 Each unit requires 0.15mA when dimming funcon is used. Please make sure your controller is capable of
driving the units.

Installaon Manual
3
1
2
4
( )9 Suggested fuse and maximum number of the DRA that can be connected to a circuit breaker at 230V are shown
as below.
Model
Fuse
Circuit breaker
C16
D 16
DRA- 40
T2.5A/L250V
11
21
DRA- 60
T2.5A/L250V
8
16
( )10 Mounng Instrucon :
Mount as shown in gure only, with input terminals down, or else sucient cooling will not be possible.
Admissible DIN rail:TS35/7.5 or TS35/15
For rail fastening :
( )a Tilt the unit slightly rearwards.
( )b Fit the unit over top hat rail.
( )c Slide it downward unl it hits the stop.
( )d Press against the bottom for locking.
( )e Shake the unit slightly to check the locking acon.
( )11 For other informaon about the products, please refer to www.meanwell.com for details.
Warning / Cauon !!
( )1Risk of electrical shock and energy hazard. All failure should be examined by a qualied technician. Please do
not remove the case of the power supply by yourself!
( )2Risk of electric arcs and electric shock (danger to life). Connecng both t primary and the secondary sides he
together is not allowed.
( )3Risk of burn hazard. Do not touch the unit in operaon and shortly aer disconnecon!
( )4 Risk of re and short circuit. The openings should be protected from foreign objects or dripping liquids.
( )5 Only install the unit in a polluon degree 2 environment (Note.1).
( )6 Please do not install the unit in places with high moisture or near the water.
( )7The maximum operang temperature is 45 for the DRA- - , for the DRA- -24, DRC-60A and °C 60 12 50°C 60
DRC-60B, for the DRA- -12/24, DRC-40A and DRC-40B, please do not install the unit in places with high 55°C 40
ambient temperature or near re source.
( )8 The FG ( ) must be connected to (Protecve Earth). PE
( )9 Output current and output waage must not exceed the rated value on its specicaon.
"Click"
Produkt Specifikationer
Mærke: | Mean Well |
Kategori: | Ikke kategoriseret |
Model: | DRA-40-12 |
Bredde: | 40 mm |
Dybde: | 100 mm |
Højde: | 90 mm |
Vægt: | 280 g |
Antal pr. pakke: | 42 stk |
Udgangseffekt: | 40 W |
Udgangsspænding: | 12 V |
Bæredygtighedscertifikater: | RoHS |
Indgangsspænding: | 90 - 264 V |
Har du brug for hjælp?
Hvis du har brug for hjælp til Mean Well DRA-40-12 stil et spørgsmål nedenfor, og andre brugere vil svare dig
Ikke kategoriseret Mean Well Manualer

12 Januar 2025

11 Januar 2025

11 Januar 2025

11 Januar 2025

5 Januar 2025

3 Januar 2025

3 Januar 2025

29 December 2024

12 December 2024

8 September 2024
Ikke kategoriseret Manualer
- Ikke kategoriseret Minuteman
- Ikke kategoriseret Aplic
- Ikke kategoriseret Panduit
- Ikke kategoriseret Drake
- Ikke kategoriseret Crazy Tube Circuits
- Ikke kategoriseret Deye
- Ikke kategoriseret Monzana
- Ikke kategoriseret Bearware
- Ikke kategoriseret Lupine
- Ikke kategoriseret Glide Gear
- Ikke kategoriseret Computherm
- Ikke kategoriseret Lorex
- Ikke kategoriseret Edesa
- Ikke kategoriseret Blue
- Ikke kategoriseret Uniropa
Nyeste Ikke kategoriseret Manualer

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025