Tripp Lite PDU3MV6L2120 Manual

Tripp Lite stikdase PDU3MV6L2120

Læs gratis den danske manual til Tripp Lite PDU3MV6L2120 (36 sider) i kategorien stikdase. Denne vejledning er vurderet som hjælpsom af 9 personer og har en gennemsnitlig bedømmelse på 5.0 stjerner ud af 5 anmeldelser. Har du et spørgsmål om Tripp Lite PDU3MV6L2120, eller vil du spørge andre brugere om produktet?

Side 1/36
1
Owner’s Manual
3-Phase Metered
Power Distribution Units
Important Safety Insructions 2
Installation 3
Digital Load Meter 6
Features 7
Service 8
Warranty and Product Registration 9
Español 10
Français 19
 28
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2015 Tripp Lite. All rights reserved.
PDU3MV6L2120
(Series Number: AGPD8414)
PDU3MV6L2120LV
(Series Number: AGPD8414)
PDU3MV6L2120B
(Series Number: AGPD8414)
PDU3MV6L2130
(Series Number: AGPD8415)
PDU3MV6H50
(Series Number: AGPD8416)
PDU3MV6H50A
(Series Number: AGPD8417)
PDU3XMV6G20
(Series Number: AGPD8420)
PDU3XMV6L2220
(Series Number: AGPD8420)
PDU3MV6L2130A
(Series Number: AG-00E3)
15-07-049-933145.indb 1 8/7/2015 1:58:11 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during
the installation, operation, and storage of this product. Failure to heed these
instructions and warnings may affect the product warranty.
The PDU provides convenient multiple outlets, but it DOES NOT provide surge or line noise
protection for connected equipment.
The PDU is designed for indoor use only in a controlled environment away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
The power requirement for each piece of equipment connected to the PDU must not exceed
the individual outlet’s load rating.
The total power requirement for equipment connected to the PDU must not exceed the
maximum load rating for the PDU.
Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
Do not attempt to modify the PDU, including the input plugs and power cables.
Do not attempt to use the PDU if any part of it becomes damaged.
Do not attempt to mount the PDU to an insecure or unstable surface.
Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Never attempt to install electrical equipment during a thunderstorm.
Keep indoor ambient temperature between 32°F and 104°F (0°C and 40°C).
Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
Do not attempt to open the PDU; there are no user-serviceable parts inside.
The PDU must be installed by a qualified technician only.
Install in accordance with National Electrical Codes. Be sure to use the proper over current
protection for the installation, in accordance with the plug rating/equipment rating.
The electrical sockets supplying power to the equipment shall be installed near the equipment
and be easily accessible.
15-07-049-933145.indb 2 8/7/2015 1:58:11 PM


Produkt Specifikationer

Mærke: Tripp Lite
Kategori: stikdase
Model: PDU3MV6L2120
Vekselstrømsindgangsfrekvens: 60 Hz
Bredde: 55.9 mm
Dybde: 49 mm
Højde: 1778 mm
Vægt: 5730 g
Produktfarve: Sort
Pakkevægt: 6990 g
Pakkedybde: 1935.5 mm
Pakkebredde: 172.7 mm
Pakkehøjde: 137.2 mm
Relativ luftfugtighed ved drift (H-H): 0 - 95 %
Husmateriale: Stål
Dimensioner (BxDxH): 49 x 56 x 1778 mm
Certificering: UL60950-1, NOM
Kabellængde: 1.83 m
Pakkens dimensioner (BxDxH): 155 x 110 x 1925 mm
Bæredygtighedscertifikater: RoHS
Oprindelsesland: Taiwan
Produkter pr. hovedkasse (udvendigt): 1 stk
Montering: Lodret
Strømstik: NEMA L21-20P
Nominel udgangsspænding: 120 V
Nominel indgangsspænding: 208 V
Load-kapacitet: 5700 VA
Maksimal strømtræk pr. fase: 9.2 A
AC udgange, antal: 48 AC stikkontakt(er)
Rackkapacitet: 0U
Strøm (maks.): 16 A
PDU-typer: Målte
Overvågning: Strøm

Har du brug for hjælp?