BlueSolar PWM Light Charge Controller 12/24V 
(with light turn-off timer)  
 
 
Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands 
Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sales@victronenergy.com 
Date : 02-05-2017
1. DESCRIPTION 
 
•  Programmable load output with lighting control mode. 
•  Three stage battery charging (bulk – absorption – float). 
•  Protected against over current. 
•  Protected against short circuit. 
•  Protected against reverse polarity connection of the battery or solar array. 
•  Low voltage load disconnect. 
•  Easy to set up thanks to two digit seven segment display. 
 
2. INSTALLATION 
 
The display will show a ‘’12’’ if the Controller detects a 12V battery, and a “24” if 
it detects a 24V battery 
 
Do not exceed Solar and Load ratings 
3. LED INDICATORS 
Green LED:  
Off: No sunlight or not enough sunlight. Charger off. 
Fast flashing: Bulk charge. 
On: Absorption charge. 
Slow flashing: Float charge. 
 
LED=Green: battery fully charged (> 12,7V) 
LED=Orange: battery ok (12,4V - 12,7V) 
LED=Red: battery low (11,2V - 12,4V) 
LED=Flashing Red: battery fully discharged (< 11,2V) 
               (load output cut off level: 11,2V) 
 
LED=ON: load output is on.  
LED=OFF: load output is off. 
LED=Slow flashing: Overload. 
LED=Fast flashing: Short Circuit 
 
Please note: 
1. The load output will cut off in case of over load or short circuit. The load output 
will attempt to restart after 30 seconds. 
2. After over discharge, the load will reconnect automatically when the battery is 
recharged to 13,1V / 26,2V. 
3. After over discharge, the load can be reconnected manually by pressing the 
on/off push button, if the battery voltage exceeds 12,6V / 25,2V. 
 
4. SETTING THE LOAD OUTPUT 
 
4.1 Settings 
 
 
 
 
 
 
 
 
 
 
 
 
 
4.2 Settings description 
 
0  Charger only 
The load output is switched off permanently. 
 
1-13  Light control + delay 
The load output automatically turns on after sunset (array voltage < 4V) and the 
built-in timer starts counting. 
When the timer reaches the set time, or when the low voltage limit is reached, 
the load output will turn off. 
 
H  Manual 
The load output can be turned on and off manually with the push button. 
(low voltage shutdown remains active) 
 
C  Load output controlled by battery voltage only 
Load disconnect and load reconnect will be based only on battery voltage, see 
section 3 
 
L  Dusk to dawn mode 
Turn on delay (array voltage < 4V): 10 seconds. 
Turn off delay (array voltage > 4V): 1 minute. 
No timer function. 
 
d  Debug mode 
Same as L mode but without delay of 10s/1min 
 
5. SPECIFICATIONS 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
BlueSolar PWM-Light 12/24-5  12/24-10 12/24-20 12/24-30 
Battery Voltage 12/24V with automatic system voltage detection* 
Rated charge current 5 A 10 A 20 A 30 A 
  Recommended solar array
 
36 cell for 12 V / 72 cell for 24 V 
Automatic low voltage load 
disconnect Yes 
Maximum solar voltage 28 V for a 12 V system and 55 V for a 24 V system  (1) 
Self-consumption < 10 mA 
Overload protection 
Shut down after 60 s in case of 130% load 
Shut down after 5 s in case of 160% load  
Short circuit: immediate shut down 
Grounding Common positive 
Operating temp. range  -20 to +50°C (full load) 
Humidity (non condensing)  Max 95 % 
Settings 
Charge voltage 'absorption' 14.2 V / 28,4 V 
Charge voltage 'float' 13.8 V / 27,6 V 
Load disconnect 11,2V / 22,4V 
Load reconnect 12,6V / 25,2V (manual) 
13,1V / 26,2V (automatic) 
Protection class IP20 
Terminal size 5 mm² / AWG10 
Weight 0,13 kg 0,15 kg 
Dimension (h x w x d) 70 x 133 x 33,5 mm (2.8 x 5.3 x 1.3 inch) 
Mounting Vertical wall mount        Indoor only 
Humidity (non condensing)  Max. 95% 
Operating temperature  -20°C to +50°C (full load) 
Cooling Natural convection 
Standards 
Safety IEC 62109-1 
EMC EN 61000-6-1, EN 61000-6-3, ISO 7637-2 
 
1) For 12V use 36 cell solar panels 
    For 24V use 72 cell solar panels 
    or 2x 36 cell in series 
2) The controller switches to the lower float 
voltage level 2 hours after the absorption voltage 
has been reached. 
Whenever the battery voltage becomes lower 
than 13 V, a new charge cycle is triggered. 
 
0  Load output permanently off  9 
Load output turned on during 9 
hours after sunset 
1 
Load output turned on during 1 
hour after sunset 
10 
Load output turned on during 10 
hours after sunset 
2 
Load output turned on during 2 
hours after sunset 
11 
Load output turned on during 11 
hours after sunset 
3 
Load output turned on during 3 
hours after sunset 
12 
Load output turned on during 12 
hours after sunset 
4 
Load output turned on during 4 
hours after sunset 
13 
Load output turned on during 13 
hours after sunset 
5 
Load output turned on during 5 
hour after sunset 
H  Manual load control 
6 
Load output turned on during 6 
hours after sunset 
C 
Load output controlled by battery 
voltage only 
7 
Load output turned on during 7 
hours after sunset 
L  Dusk to dawn mode 
8 
Load output turned on during 8 
hours after sunset 
d  Debug mode 
• Always connect the batteries first, in order to allow the 
Controller to recognize system voltage 
 
• Use a 12V (36 cells) solar array for a 12V battery system. 
 
• Use a 24V (72 cells) solar array for a 24V battery system.