Læs gratis den danske manual til Carrier AquaSnap 30MP (80 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 5 personer og har en gennemsnitlig bedømmelse på 4.7 stjerner ud af 3 anmeldelser. Har du et spørgsmål om Carrier AquaSnap 30MP, eller vil du spørge andre brugere om produktet?

Side 1/80
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300290-01 Printed in U.S.A. Form No. 30MP-32SI Pg 1 6-25 Replaces: 30MP-31SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mounting Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Minimum Area Requirements for Installation and
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
UNVENTILATED AREA
NATURAL VENTILATION TO OCCUPIED SPACE
NATURAL VENTILATION TO THE OUTDOORS OR
UNOCCUPIED SPACE
MECHANICAL VENTILATION
MECHANICAL VENTILATION – REFRIGERANT
LEAK DETECTOR
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . 30
Step 2 — Position the Unit . . . . . . . . . . . . . . . . . . . . 30
Step 3 — Place the Unit . . . . . . . . . . . . . . . . . . . . . . 30
Step 4 — Check Compressor Mounting . . . . . . . . . 30
30MP 017-031, 041, AND 046 UNITS
30MPW 033 UNITS
30MP 051-080 UNITS
Step 5 — Make Piping Connections . . . . . . . . . . . . 31
SAFETY PRECAUTIONS FOR WORKING WITH
REFRIGERANT
UNITS WITHOUT MANIFOLD
30MPA SYSTEM CONDENSER
30MPW/MPQ UNITS WITH NITROGEN CHARGE
EVACUATION AND DEHYDRATION
30MPW/MPQ CONDENSER DESCRIPTION
30MPW/MPQ CONDENSER
CONDENSER WATER CONTROL VALVE
EVAPORATOR DESCRIPTION
EVAPORATOR PIPING
CHILLED WATER FLOW SWITCH
FOR UNITS WITH WATER MANIFOLD
DUAL CHILLER CONTROL OPTION
MULTI-UNIT CHILLER CONTROL ACCESSORY
•AIR SEPARATION
Step 6 — Fill the Chilled Water Loop . . . . . . . . . . . 63
WATER SYSTEM CLEANING
FILLING THE SYSTEM
Step 7 — Make Electrical Connections . . . . . . . . . . 64
30MPA, MPW, MPQ CONTROL BOX
30MPE DISTRIBUTION PANEL
UNBALANCED 3-PHASE SUPPLY VOLTAGE
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location.
Only trained, qualified installers and service mechanics should
install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions,
such as cleaning coils. All other operations should be performed
by trained service personnel. Qualified installers and service tech
-
nicians are required to have been trained on the following topics
when installing and servicing air-conditioning equipment with
A2L refrigerant such as R-32:
1. Explosive potential of A2L refrigerants.
2. Potential ignition sources.
3. Safety measures for unventilated and ventilated rooms or
enclosures.
4. Refrigerant detectors.
5. Concept of sealed components and sealed enclosures
according to IEC 60079-15:2010.
6. Correct work procedures for the following:
a. Commissioning
b. Maintenance
c. Repair
d. Decommissioning
e. Disposal
See Controls and Troubleshooting Guide for complete guidelines.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
1. Follow all safety codes.
2. Keep quenching cloth and fire extinguisher nearby when
brazing.
3. Wear safety glasses and work gloves.
4. Use care in handling, rigging, and setting bulky equipment.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
AquaSnap
®
30MPA021-080, MPW017-080 and 30MPQ021-080
Liquid Chillers with Scroll Compressors
and PIC6 Controls
2
NOTE: Refer to the following symbols, which are required for
A2L refrigerants and can be found on the unit:
GENERAL
These installation instructions cover the 30MPA, 30MPW, and
30MPQ units with PIC6 controls. The 30MPA units are condens-
erless units and the 30MPW/30MPQ units are fluid cooled. See
Fig.
1-4 for different unit configurations. See Fig. 5 and 6 for mod-
el number nomenclatures and Fig. 7-24 for unit dimensional de-
tails and corner weights.
SYMBOL CODE MEANING
IEC 60417-5032 (2002-10) Alternating Current
IEC 60417-5019 (2006-8) Protective Earth
IEC 60417-5018 (2006-10) Functional Earthing
ISO 7000-0434A (2004-01) Caution
ISO 7000-0790 (2004-01)
Read Operator’s
Manual
IEC 60417-5036 (2002-10) Dangerous Voltage
GHS02: Flammable Flammable Gas
ISO 7010-W021 (2011-05)
Warning: Flammable
Materials
ISO 7000-1659 (2004-01)
Service Indicator:
Read Technical
Manual
ISO 7000-1701 (2004-01) Pressure
ISO 7000-1641 (2004-01)
Operator’s Manual:
Operating
Instructions
WARNING
DO NOT use means to accelerate the defrosting process, or to
clean, other than those recommended by the manufacturer.
If unit is to be stored, it shall be stored in an area or room
without continuously operating open flames (for example, an
operating gas appliance) or other potential ignition sources,
such as operating electric heaters or hot surfaces.
Do not pierce or burn.
Be aware that refrigerants may not contain an odor.
IMPORTANT: This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in
accordance with these instructions, may cause radio interference.
It has been tested and found to comply with the limits of a
Class A computing device pursuant to International Standard in
North America EN 61000-2/3, which are designed to provide
reasonable protection against such interference when operated in
a commercial environment.
WARNING
This product can expose you to chemicals including lead and
lead components, which are known to the State of California
to cause cancer and birth defects or other reproductive harm.
For more information, go to www.P65Warnings.ca.gov.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gauge for how
much oil to add to the system.
e. Carefully un-sweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal inju-
ry or death.
WARNING
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation and service.
There may be more than one disconnect switch. Tag all
disconnect locations to alert others not to restore power until
work is completed.
CAUTION
DO NOT re-use compressor oil or any oil that has been ex-
posed to the atmosphere. Dispose of oil per local codes and
regulations. DO NOT leave refrigerant system open to air any
longer than the actual time required to service the equipment.
Seal circuits being serviced and charge with dry nitrogen to
prevent oil contamination when timely repairs cannot be com
-
pleted. Failure to follow these procedures may result in dam-
age to equipment.
CAUTION
This system uses an A2L refrigerant (R-32) which have
higher pressures than R-22 and other refrigerants. No other
refrigerant can be used in this system. Failure to use gauge
set, hoses, and recovery systems designed to handle
refrigerant R-32 may result in equipment damage or
personal injury. Refer to 30MP Controls, Start-up, Service,
and Troubleshooting for guidelines on proper A2L
refrigerant handling and equipment used for A2L
refrigerant. If unsure about equipment, consult the
equipment manufacturer.