Læs gratis den danske manual til Carrier AquaSnap 30RA (28 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 6 personer og har en gennemsnitlig bedømmelse på 3.8 stjerner ud af 3.5 anmeldelser. Har du et spørgsmål om Carrier AquaSnap 30RA, eller vil du spørge andre brugere om produktet?

Side 1/28
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300016-01 Printed in U.S.A. Form 30RA-17SI Pg 1 1-08 Replaces: 30RA-12SI
Book 2
Ta b 5 c
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-24
Step 1 — Rig and Place the Unit. . . . . . . . . . . . . . . . . . 1
•RIGGING
•PLACING UNIT
MOUNTING UNIT
Step 2 — Check Compressor Mounting . . . . . . . . . . 3
Step 3 — Cooler Fluid and Drain Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ALL UNITS
UNITS WITH FACTORY-INSTALLED
HYDRONIC PACKAGES
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . . . 12
•AIR SEPARATION
WATER SYSTEM CLEANING
FILLING THE SYSTEM
PREPARATION FOR YEAR-ROUND OPERATION
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . . 18
POWER SUPPLY
•POWER WIRING
FIELD CONNECTIONS
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . . 24
ELECTRICAL
Step 7 — Check Refrigerant Circuit . . . . . . . . . . . . . 24
LEAK TESTING
DEHYDRATION
REFRIGERANT CHARGE
APPENDIX A (Pressure Drop Curves,
30RA010-055) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-27
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated struc-
tures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when
brazing.
Use care in handling, rigging, and setting bulky
equipment.
INSTALLATION
Step 1 — Rig and Place the Unit
RIGGING Preferred method for rigging is with spreader
bars from above the unit. Use hooks in lifting holes. Rig at a
single point with 4 cables or use spreader bars. All panels must
be in place when rigging. See rigging label on unit for details
concerning shipping weights, distance between lifting holes,
center of gravity, and lifting ring dimensions. See Tables 1A
and 1B for physical data. Refer to Fig. 2 for unit weights.
See Fig. 3 for rigging label.
If overhead rigging is not possible, place chiller on skid or
pad for rolling or dragging. When rolling, use a minimum of
3 rollers. When dragging, pull the pad. Do not apply force to
the unit. When in final position, raise from above to lift unit
off pad.
PLACING UNIT There must be at least 3 ft (0.9 m) for
service and for unrestricted airflow on all non-coil sides of unit,
and a minimum of 3.5 ft (1.1 m) clear air space on coil sides.
For multiple units, allow 8 ft (2.48 m) separation between units
for airflow and service.
MOUNTING UNIT When unit is in proper location, use
of mounting holes in base rails is recommended for securing
unit to supporting structure, or for mounting unit on vibration
isolators if required. See Fig. 3. Fasteners for mounting unit are
field supplied. Be sure unit is level to within
1
/
8
in. per foot for
proper oil return to compressor.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
All panels must be in place when rigging. Damage to unit
could result.
AQUASNAP
®
30RA010-055
Liquid Chillers
with COMFORTLINK
TM
Controls
Fig. 1 — Typical 30RA Unit (010-018 Shown)