
2.3PanelMounting
1
2
1-Before mounting the device in your
panel, make sure that the cut-out is of
the right size.
2-Insert the device through the cut-out.
If the mounting clamps are on the unit,
put out them before inserting the unit to
the panel.
2.4InstallationFixingClamp
1
2
The unit is designed for panel mounting.
1-Insert the unit in the panel cut-out from
the front side.
2- Insert the mounting clamps to the
holes that located left and right sides of
the device and make the unit completely
immobile within the panel
2.5RemovingfromthePanel
2
1
Loosen the screws
1-Pull mounting clamps from left and
right fixing sockets.
2-Pull the unit through the front side of
the panel
Montage of the unit to a system must be
done with it’s own fixing clamps. Do not
do the montage of the device with
inappropriate fixing clamps. Be sure
that device will not fall while doing the
montage.
c
5
3. ElectricalWiringDiagram
3.1SupplyVoltageInputConnectionoftheDevice
1
LN
2
Y
c
a
Make sure that the power supply voltage is same indicated on the instrument. Switch on the power supply
only after that all the electrical connection have been completed. Supply voltage range must be determined
in order. While installing the unit, supply voltage range must be controlled and appropriate supply voltage
must be applied to the unit. Controlling prevents damages in unit and system and possible accidents as a
result of incorrect supply voltage.
There is no power supply switch or fuse on the device. So a power supply switch and a fuse must be added
to the supply voltage input. Power supply switch and fuse must be put to a place where user can reach
easily. Power supply switch must be two poled for seperating phase and neutral. On/Off condition of power
supply switch is very important in electrical connection. On/Off condition of power supply switch must be
signed for preventing the wrong connection.
External fuse must be on phase connection in supply input.
External fuse must be on (+) line connection in supply input.
V
Z
Note-3
Note-2
100...240V (-%15;+%10)50/60Hz2VA orV
24V (-%15;+%10)50/60Hz2VA orV
24V (-%15;+%10)2WZ
Note-1
100...240V (-%15;+%10)50/60Hz2VAV
24V (-%15;+%10)50/60Hz2VAV
24V (-%15;+%10)2WZ
The instrument is protected with an internal fuse (Please refer to Note-1 for information). In
case of failure it is suggested to return the instrument to the manufacturer for repair.
c
6
AnalogueOutput
SupplyVoltageInput
(0/2...10V )orZ
(0/4...20mA )Z
Note-2: “L” is (+), “N” is (-) for 24V Supply
Voltage
Z
SupplyVoltage
Power
Supply
Switch
External
Fuse
(1 A T)
Note-3: External Fuse is recommended
Note-1:Thereisaninternal33R fusible
flameproofresistorin
Thereisaninternal4R7 fusibleflameproof
resistorin
W
W
100-240V 50/60Hz
24V 50/60Hz
V
W
7
8
4.ÖnPanelinTanýmýveMenülereEriþim
Software
revision
number
OperationScreenisshown
c
Note-1: If increment or decrement button is pressed for 2 seconds continuously, increment and
decrement number become 10, if pressed for 4 seconds continuously, increment and decrement
number become 100, if pressed for 6 seconds continuously, increment and decrement number
become 1000.
4.FrontPanelDefinitionand AccessingtotheMenus
When power is first applied to the Digital Power Regulator, software revision number is shown on
the display.
If there is an unexpected situation while opening the device, power off the
device and inform a qualified personnel.
4.1ObservationofSoftwareRevisionontheDisplay
“rv” RevisionÞ
9
OperationScreen
SETValueScreen
SETValueScreen
NewSetvalueisshownonthedisplay
Displaystopblinkingandoperation
screenisshown
SET Value can be adjusted from minimum set value parameter to maximum set value
parameter , they can be accessed from programming parameters.
i
4.2.2 ChangingandSavingSetValueWhileTheDeviceisnotRunning
Ýf Set value is changed while the device is running, analogue output is affected
simultaneously by change on the set value. Analogue output increases or decreases
to the new set value according to the and parameters.
i
4.2.1 ChangingandSavingSetValueDeviceisRunning
4.2ChangingandSavingSetValue
WhenIncrementandDecrement
buttonsarepressed,SET valueis
shownonthedisplay,anddisplay
startstoblink
ChangetheSET valuewith
incrementanddecrement
buttons.
OperationScreen
ifnobuttonispressedfor5
seconds,setvalueissaved.
If no operation is performed in Set value changing mode for 5 seconds, device turns
to operation screen automatically.
10
4.3.ProgramParameters
5.1.SETParametresi
Scale Low Limit Parameter ( Default = 0.0 )
It can be adjusted from -1999 to ( -1). At this value analogue output
becomes;
If=0,accordingtothedevicetype0V or0mA
If=1,accordingtothedevicetype2V or4mA
Z Z
Z Z
(1)
(2)
(1)
(2)
Scale High Limit Parameter:( Default = 100.0 )
It can be adjusted from ( +1) to 9999. At this value analogue output
becomes;
According to the device type10V or 20mAZ Z
(1) (2)
Set Low Limit Parameter:( Default = 0.0 )
Set value can not be defined less than this value.
It can be adjusted from Scale low limit parameter value to Set high
limit parameter value.
Set High Limit Parameter:( Default = 100.0)
Set value can not be defined greater than this value.
It can be adjusted from Set low limit parameter value to Scale high
limit parameter value.
Decimal Point Position Parameter:( Default =1)
Decimal point position is determined with this parameter. It can be adjusted
from 0 to 3.
Power On Output Control Parameter: ( Default = 2)
When power on firstly, Analogue and digital outputs status can be determined
with this parameter. It can be adjusted from 0 to 2.
= Device does not start to operate, Analogue output is equal to the Set low limit
value.
POWER
ON
OFF
ANALOGUE
OUTPUT
POWERON
=Devicestartstooperate, AnalogueoutputisequaltotheSetvalue.
POWER
ON
OFF
ANALOGUE
OUTPUT
POWERON
i
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z
Z
analogue output.
analogue output.
(1)
(2)
0V
(1)
(2)
Su-L V
/Su-L mA
/0mA
(1)
(2)
Figure-4.1 (Strt=0)PowerOnBehaviour
Figure-4.2 PowerOnBehaviour(Strt=1)
0V
(1)
(2)
Su-L V
/Su-L mA
/0mA
(1)
(2)
11
POWER
ON
OFF
POWERON
=Devicestartstooperate, AnalogueoutputisincreasedfromtheScaleSet
lowlimittoSetvalueaccordingtotherampuptime.
ANALOGUE
OUTPUT
ANALOGUE
OUTPUT
For=
For=
0V
(1)
(2)
SetV
/SetmA
/0mA
(1)
(2)
2V
/4mA
(1)
(2)
0V
/0mA
(1)
(2)
(1)
(2)
SetV
/SetmA
Figure-4.3 (Strt=2)PowerOnBehaviour
Tup
Tup
Tup=
rut
X
(Set-LoL)
(uPL -LoL)
(sec)
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z
Z
analogue output.
analogue output.
(1)
(2)
Ramp Up Time Parameter:( Default = 10sec )
Increasing time of the analogue output from 0V 10V
0mA 20mA is determined with this parameter.
It can be adjusted from 0 to 6000.
Z Z
Z Z
value to value or
from value to value
Ramp Down Time Parameter:( Default = 10sec )
Decreasing time of the analogue output from 10V 0V
0mA 0mA is determined with this parameter.
It can be adjusted from 0 to 6000.
Z Z
Z Z
value to value or
from 2 value to value
(1) (1)
(2)
(2)
(2)(2)
(1) (1)
12
Set Changing Value Parameter:( Default = 4 )
Changing value for Set value is determined with this parameter.
Set changing value become one(1)
Set changing value become ten(10)
Set changing value become hundred(100), for each pressing the
Increment, Decrement button
Set changing value become incremental. (Note-1)
Analogue Output Range Selection Parameter:( Default = 0 )
Analogue output range is determined with this parameter
according to the device type 0...10V or 0...20mA
according to the device type 2...10V or 4...20mA
Z Z
Z Z
(2)(1)
(1) (2)
Adjustment SectionAccessing Password:
Required password is entered via this parameter for accessing to the
adjustment section. If the parameter value is entered as 3083, screen
is accessed, otherwise parameter is seen
Adjustment Value Parameter:
Adjustment value forAnalogue output. It can be adjusted from 0 to 4095.
When pressing button on screen, adjustment value is seen on
screen. The value on the screen should be adjusted with Increment and
decrement button until 10.00V or 20.00mA s obtained from the
analogue output.
After getting the 10.00V or 20.00mA
Z Z
Z Z
i
on analogue output, press
button for saving this value as an adjustment value
Programming SectionAccessing Password:( Default =0 )
It is used for entering to the programming section.
It can be adjusted from 0 to 9999. If this password is 0, programming section
can be accessed without entering the password.
(2)
(1)
SET
(1) (2)
i
Note-1 : If increment or decrement button is pressed for 2 seconds continuously, increment
and decrement number become 10, if pressed for 4 seconds continuously, increment and
decrement number become 100, if pressed for 6 seconds continuously, increment and
decrement number become 1000.
Error InputActive on Delay Parameter :( Default = 0 )
When the error input is active ,this parameter indicates the delay time for the
device to be in error mode.It can be adjusted from 0 to 9999 seconds.
Error Input Passive on Delay Parameter :( Default = 0 )
When the error input is passive ,this parameter indicates the delay time for the
device to leave the error mode.When this parameter is 9998,if the increment
button is pressed is observed and error latching is selected.The device
stays in error mode even if error condition is disappared.In order to make Error
latching passive the decrement button must be pressed in Main Operation
Screen.It can be adjusted from 0 to 9999 seconds.
P
RUN
%
P
RUN
%
P
RUN
%
RUN
%
5sec.
OperationScreen
SETValueScreen
WhenIncrementandDecrement
buttonsarepressed,SET valueis
shownonthedisplay,anddisplay
startstoblink
P
RUN
%
P
RUN
%
SETValueScreen
Displaystopblinkingandoperation
screenisshown.
OperationScreen
ifnotpressedanybuttonfor5
seconds,setvalueissaved.
P
RUN
%
RUN
%
5sec.
PowerRegulator
EPR-3790
%
RUN
P
PowerRegulator
EPR-3790
%
RUN
P
PowerRegulator
EPR-3790
%
RUN
P
DisplaysSetValue
andParameters
LedIndication
ofStart
ItisusedasStart/Stop
Buttonandalso
ItisusedasEnter
buttoninprogramming
mode.
Itisusedtoenterthe
programmingandset
valuechangingmodes
aswellas
incrementationand
accessingtothe
parametersin
programmingmode.
Note-1
Ledindicationof
ProgrammingModeisactive
LedIndication
ofError
Itisusedtoenterthe
programmingandsetvalue
changingmodesaswellas
decrementation
4.4.DeviceStart/StopOperation
OperationScreen
When S
While the device is running if Start/Stop button is
pressed again s
led lights off, a
tart/Stop button is pressed, Set value is
seen on display, Run led lights on, selected
analogue output starts to increase from the set
low limit value to set value during time
with ramp.
et low limit value is seen on
display, Run nalogue output starts
to decrease from set value to set low limit
value.during time.
Tup(sec)
Tdown(sec)
%
RUN
P
ProgrammingSection
AccessingScreen
PasswordEnteringScreen
Pressincrement
buttonforaccessing
tothepassword
enteringscreen
When
buttonsarepressedfor5seconds,
”P”ledstartstoblink.Ifprogramming
sectionaccesspasswordisset
Programmingsectionaccessscreen
isobserved
incrementanddecrement
Enterprogrammingsection
accessingpasswordwith
Incrementanddecrementbuttons
PressI/Obuttontosubmitthe
password.
4.5EnteringToTheProgrammingMode,ChangingandSavingParameter
i
ScaleLowLimitParameterValue
ScaleLowLimitParameterValue
ScaleLowLimitParameter
Parametervalueisaccessedbypressing
incrementbutton.Ifsetbuttonispressed,
nextparameterisshown.
Changetheparametervalue
withincrementanddecrement
buttons
PressI/Obuttonforsavingthe
parametervalue
If no operation is performed in programming mode for 20 seconds, device turns to
main operation screen automatically.
Note-2: Parameters can be observed by pressing SET button in programming section
accessing screen without entering programming section accessing password. But
parameters can not be changed.
Note-1: Ifprogrammingsectionaccessingpasswordis=0,scalelowlimit
parameterscreenisobservedinsteadofprogrammingsectionaccessing
PasswordEnteringScreen
OperationScreen
P
RUN
%
RUN
P
%
RUN
P
%
RUN
P
%
RUN
P
%
RUN
P
%
RUN
P
%
ChangetheSET valuewith
incrementanddecrement
buttons.
TimeUnitSelection Parameter:(Default=0)
Counts in Second
Counts in Minute
SoakTimeParameter:(Default=0sec)
Soaktimeisactivetedunlesssoakparameterisentered0. Afterramp
timeisup,theoutputremainsactiveforsoaktimeandoutputreturnsto0.It
canbeselectedbetween0and6000.
ButtonProtectionParameter:(Default=0)
Buttons protection is passived.
Start-Stop Button protection is actived.
ErrorInput
2
P/N:EPR-3790-2.00.0.5/00.00/1.0.0.0
Y
c
a
3
41
5 6
7
8 9
10 11 12
L(+)
N(-)
0/2...10V OUTPUTZ
GND
ERROR DOWN
UP
DigitalDown
DigitalUp