24 HR. DIAL TIME SWITCH (SPST)
WITH INDEPENDENTLY WIRED CLOCK MOTOR
40 A RESISTIVE, 120-480 VAC;
40 A INDUCTIVE, OR TUNGSTEN OR
1000 VA PILOT DUTY 120 VAC;-277
2 HP (24 FLA)-120 VAC; 5 HP (28 FLA) - 240 VAC.
16 A ELECTRONIC BALLAST, 277 VAC
75°C INSULATION MAX. MOTOR
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Use wires rated at least 90°C - COPPER conductors ONLY.
• Replace plastic insulator covering terminals before powering ON.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
Risque d’incendie ou de choc électrique
• Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-
DIAL ON OFF, pointing to time (AM or PM) when and operations are desired,
tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction
and align the exact time-of-day on the (the time now, when CLOCK-DIAL
switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
TO OPERATE SWITCH MANUALLY: MANUAL LEVERMove
DIAL left or right as indicated by arrows. This will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day.
See programming instructions.
SPRING GROVE, ILLINOIS 60081-9698
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER only. May use two wires of the same size and type.conductors