MODEL: T103R
24 HOUR DIAL TIME SWITCH
TYPE 3R RAINPROOF ENCLOSURE
SUITABLE FOR POOL EQUIPMENT CONTROL IF
INSTALLED 5 FT. OR MORE FROM EDGE OF POOL.
40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VAC
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER
REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--02001
UL
HOLOGRAM
LABEL
LR3730
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER only. May use two wires of the same size and type.conductors
WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Use wires rated at least 90°C - COPPER conductors ONLY.
• For outdoor locations, raintight, or wet location, conduit hubs that comply with requirements of
UL514B (standard for fittings for conduit and outlet boxes) are to be used.
• Replace plastic insulator covering terminals before powering ON.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
• Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
• Pour les emplacements extérieurs, étanches à la pluie ou les emplacements mouillés, des entrées de
conduit qui sont conformes aux exigences de UL514B (norme pour les pièces de fixation pour conduit
et boîtes de sortie) doivent être utilisées
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-
DIAL ON OFF, pointing to time (AM or PM) when and operations are desired,
tighten tripper screws firmly. For additional tripper pairs on order CLOCK-DIAL
156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and
align the exact time-of-day on the (the time now, when switch is CLOCK-DIAL
being put into operation) to the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
•
TO OPERATE SWITCH MANUALLY: MANUAL LEVERMove
CLOCK-DIAL below
left or right as indicated by arrows. This will not effect next operation.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See
programming instructions.
TYPICAL
WIRING
DIAGRAM
CLOCK
MOTOR
120/240
VOLT
3 WIRE
SUPPLY
TO
LOADS
GROUND
LINE 2
LINE 1
A
4
2
GR.
3
1
NEUT.
Produkt Specifikationer
Mærke: | Intermatic |
Kategori: | bryter |
Model: | T103R |
Har du brug for hjælp?
Hvis du har brug for hjælp til Intermatic T103R stil et spørgsmål nedenfor, og andre brugere vil svare dig
bryter Intermatic Manualer

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025

7 Juni 2025
bryter Manualer
- bryter Finder
- bryter Televés
- bryter CyberPower
- bryter APC
- bryter Smart-AVI
- bryter Yamaha
- bryter InLine
- bryter Tenda
- bryter Adder
- bryter Advantech
- bryter Mercusys
- bryter TRENDnet
- bryter Lancom
- bryter Atlona
- bryter Iogear
Nyeste bryter Manualer

7 Juni 2025

6 Juni 2025

6 Juni 2025

6 Juni 2025

3 Juni 2025

2 Juni 2025

1 Juni 2025

1 Juni 2025

1 Juni 2025

1 Juni 2025