Intermatic T171 Manual


Læs gratis den danske manual til Intermatic T171 (1 sider) i kategorien bryter. Denne vejledning er vurderet som hjælpsom af 26 personer og har en gennemsnitlig bedømmelse på 5.0 stjerner ud af 13.5 anmeldelser. Har du et spørgsmål om Intermatic T171, eller vil du spørge andre brugere om produktet?

Side 1/1
MODEL: T171
24 HOUR DIAL TIME SWITCH WITH “SKIPPER
®
TYPE 1 INDOOR USE ONLY
SINGLE POLE SINGLE THROW (SPST)
40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
LINE
NEUT.
CLOCK
MOTOR
GROUND
A
1
2
GRD.
120V
SUPPLY
TO
LOAD
WIRING
DIAGRAM
WARNING
Risk of Fire or Electric Shock
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
Installation and/or wiring must be in accordance with national and local electrical code requirements.
Use wires rated at least 90°C - COPPER conductors ONLY.
Replace plastic insulator covering terminals before powering ON.
KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--02060
UL
HOLOGRAM
LABEL
LR3730
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER only. May use two wires of the same size and type.conductors
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to
time (AM or PM) when and operations are desired, tighten tripper screws firmly. ON OFF
For additional tripper pairs on order 156T1948A.CLOCK-DIAL
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align
the exact time-of-day on the (the time now, when switch is being put into CLOCK-DIAL
operation) to the pointer. DO NOT MOVE POINTER.
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): SKIPPING SCREW(S) SKIPPER Insert in
WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move
MANUAL LEVER SKIPPER WHEEL to “OFF” and rotate to locate correct day-of-week
opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced
wheel “TODAY” if it has.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: MANUAL LEVER Move below CLOCK-DIAL left or
right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE
SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO
ON/CUTOUT TRIPPER SWITCHING.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See
programming instructions.
DAY
ARROW
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON/CUTOUT
TRIPPER
SKIPPER
WHEEL
SKIPPING
SCREW


Produkt Specifikationer

Mærke: Intermatic
Kategori: bryter
Model: T171