PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at day-of-week and time-of-day when “ON” operations are
desired. Tighten tripper screws securely.
2. TO SET “OFF” TIMES, OFF place dark trippers against edge of CLOCK-DIAL at times when “OFF” operations are desired. Tighten trip-
per screws securely.
3. TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
4. TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-week and time-of-day (AM or PM) on dial with the
TIME POINTER. Some allowance may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: MANUAL LEVER Move below CLOCK-DIAL left or right as indicated by arrows. This will not affect
next automatic operation.
IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of- day, see step 4 of programming instructions.
For replacement parts contact Intermatic Customer Service or visit: www.intermatic.com
MODEL: T7801BC
SEVEN-DAY DIAL TIME SWITCH
WITH SPRING WOUND CARRY-OVER MOTOR
TYPE 1 INDOOR USE ONLY - FOUR POLE; TWO NORMALLY OPEN-TWO NORMALLY CLOSED
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
40 A RESISTIVE EACH POLE 120-480 VAC; 40 A INDUCTIVE, TUNGSTEN EACH POLE 120/208/240 OR 277 VAC;
1000 VA PILOT DUTY EACH POLE 120-277 VAC; 2 HP (24 FLA, 144 LRA) - 120 VAC; 5 HP (28 FLA, 168 LRA) -240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
WARNING
Risk of Fire or Electric Shock
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
Installation and/or wiring must be in accordance with national and local electrical code requirements.
Use wires rated at least 90°C - COPPER conductors ONLY.
Replace plastic insulator covering terminals before powering ON.
KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
Utiliser des fils classés 90°C minimum - Conducteurs en CUIVRE UNIQUEMENT.
UL
HOLOGRAM
LABEL
LR3730
CLOCK MOTOR: 120 VAC, 60 HZ.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--02089
120 V
60 HZ
LOADS
SUPPLY
WIRING DIAGRAM
GROUND
SCREW
CLOCK
MOTOR
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock motor voltage may be other than load
voltage, but must be as specified. For terminal markings, internal wiring and contact arrangements refer to wiring diagram above. To form the common
poles of a DOUBLE POLE DOUBLE THROW switch, if required, install jumpers (extend supply wires) between terminals 1-6 and 3-8. See table for gauge
selection. To make power connections Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly (2-18 in-lbs). Use solid or stranded
COPPER conductors only. May use two wires of the same size and type.