The binary input REG-K/4x230 is used to connect four
conventional 230 V devices (such as movement
detectors and light-sensitive switches) to the KNX bus.
The binary input has a bus coupler. It is installed on a
DIN rail acc. to EN 60715, with the bus connection
made via a bus connecting terminal. A data rail is not
required.
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
Connecting to installation networks
Connecting several electrical devices
Laying electric cables
Connecting and establishing KNX networks
Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
The internal device connection of the potentials is not
suitable for carrying load currents.
Only operate the device according to the specifica-
tions stated in the Technical data.
All the devices that are installed next to the binary in-
put must be equipped with basic insulation at the very
least.
Failure to follow these instruction can result in
equipment damage.
Binary input introduction
A Cover of the bus connecting terminal
B Programming button and programming LED (behind
hinged cover)
C Operational LED
D Channel status LEDs
1 Set the binary input onto the DIN rail.
2 Connect KNX.
¼
WARNING
Risk of fatal injury from electrical current.
The device could be damaged.
Safety clearance must be guaranteed in
accordance with IEC 60664-1. There must be at
least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
½CAUTION
The device could be damaged.
High voltages can cause damage. Never connect
devices with more than 230 V.
Operating and display elements
Installing the binary input
E1 N E2 E3 N E4
E 4E 2
RUNE 1 E 3
A
B
C
D
1
2
1 2
34
5 mm
230 V
4 mm
KNX
3 Connect the input cables.
When the bus voltage is connected and there is a signal
at the input, the corresponding yellow channel status
LED will light up.
|The N conductors must be connected to the
device. Inputs E1 to E4 have a common potential
(4 x N). Inputs E1 to E4 can be assigned to each
other with different phases.
1 Press the programming button.
The programming LED lights up.
2 Load the physical address and the application into
the device from the ETS.
The operating LED lights up: The application was loaded
successfully, the device is ready for operation.
V
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Cus-
tomer Care Centre in your country.
se.com/contact
Putting the binary input into operation
Technical data
Supply from KNX: DC 24 V / max.18 mA
Insulation voltage: AC 4 kV bus/inputs
Inputs
Nominal voltage: AC 230 V ±10 %, 50/60 Hz
0 signal: < 40 V
1 signal: > 160 V
Nominal current: AC approx. 7 mA
Permitted cable
length: max. 100 m/channel
Ambient temperature
Operation: -5 °C to +45 °C
Storage: -25 °C to +55 °C
Transport: -25 °C to +70 °C
Max. humidity: 93 % relative humidity, no
moisture condensation
Environment: The device is designed for use
at a height of up to 2000 m
above sea level (MSL).
Connections
Inputs, outputs: Screw terminals
Single-core: 1.5 mm2 to 2.5 mm2
Finely stranded
(with core end sleeve): 1.5 mm2 to 2.5 mm2
KNX: Bus connecting terminal
Dimensions
Height x width x
depth: 90 x 45 x 65 mm
Device width: 2.5 modules
Schneider Electric -Contact
KNX
+ - L1 L2 L3 N
E2
E3
E4
+
+
+
E1
+
-
-
Schneider Electric Limited
Telford, TF3 3 BL, UK
UK Representative
Stafford Park 5
SpaceLogic KNXBinary input REG-K/4x230
Operating instructions
Art. no. MTN644992
en
E 4E 2
RUNE 1 E 3
V6449-562-01 11/21


Produkt Specifikationer

Mærke: Schneider
Kategori: Ikke kategoriseret
Model: MTN644992

Har du brug for hjælp?

Hvis du har brug for hjælp til Schneider MTN644992 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Schneider Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer