Læs gratis den danske manual til Silent Knight SD505-6IB (1 sider) i kategorien Detektor. Denne vejledning er vurderet som hjælpsom af 32 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 16.5 anmeldelser. Har du et spørgsmål om Silent Knight SD505-6IB, eller vil du spørge andre brugere om produktet?

Side 1/1
P/N 151175
SILENT
KNIGHT
®
SD505-6IB (6” Isolator Base)
Installation Instructions
The SD505-6IB is a 6 inch isolator base that fits
underneath the 6 inch detector base.
Class A (Style 7) Configuration
An isolator base is used to isolate a short circuit
wiring fault on a Class A (Style 7) SLC loop.
Normally if the control panel detects a short on
the SLC loop the entire loop is disabled. When
isolator modules are used (as shown in Figure 1)
and a short, open or ground fault occurs on the
SLC loop, it will be detected as a trouble but all
the SLC devices will continue to operate.
Figure 1: Class A (Style 7) Example
Class B (Style 4) Configuration
Figure 2: Class B (Style 4) Example
1. If a short occurs at point A (Figure 2),
isolator base 1 will activate, isolating SLC
devices 2 and 3 from the rest of the loop.
2. If a short occurs at point B (Figure 2),
isolator base 2 will activate, isolating SLC
devices 5 and 6 from the rest of the loop.
3. If a short occurs at point C (Figure 2),
isolator base 3 will activate, isolating SLC
devices 8 and 9 from the rest of the loop.
SD505-6IB Specifications
Specification Parameter Rating
Operating Temperature: 32° - 12 F
(0° - 49° C)
Dimensions:
Length: 4-7/8”
Width 4-7/8
Depth: 7/8”
Operating Voltage: 32 VDC
Battery Current Draw dur-
ing AC loss:
Alarm/Standby: 92 uA
SLC Current: 50 uA
Max. SLC Loop Resistance: 50
For indoor use only
0-50 devices,
up to 10 per
branch