CodeRED CRG-100 Manual

CodeRED Røgalarm CRG-100

Læs gratis den danske manual til CodeRED CRG-100 (2 sider) i kategorien Røgalarm. Denne vejledning er vurderet som hjælpsom af 17 personer og har en gennemsnitlig bedømmelse på 4.9 stjerner ud af 9 anmeldelser. Har du et spørgsmål om CodeRED CRG-100, eller vil du spørge andre brugere om produktet?

Side 1/2
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user's manual contains important information about your
Smoke Alarm's operation. If you are installing this Smoke Alarm
for use by others, you must leave this manual - or a copy of it -
with the end user.
1. SUPERIOR FEATURES .....................................01
2. IMPORTANT SAFETY INFORMATION..............02
3. WHERE TO LOCATE .........................................04
4. LOCATIONS TO AVOID .....................................07
5. HOW TO INSTALL..............................................08
6. LED INDICATORS AND HORN PATTERNS......10
7. FALSE ALARM CONTROL.................................11
8. TESTING THE SMOKE ALARM .........................11
9. MAINTENANCE AND CLEANING ......................12
10. PRACTICE FIRE SAFETY..................................13
11. WHAT TO DO IN CASE OF A FIRE ...................14
12. TROUBLESHOOTING........................................15
13. LIMITATIONS OF SMOKE ALARMS..................15
14. LIMITED WARRANTY ........................................18
1. SUPERIOR FEATURES
between sleeping areas and potential sources of
fire such as living rooms and kitchens. In single
story homes with one sleeping area, a smoke alarm
should be installed in the hallway, as close as
possible to the living accommodation. To ensure
audibility in bedrooms, no smoke alarm should be
further away than 3m from any bedroom door. It
may be necessary to install more than one smoke
alarm, particularly the hallway is more than 15m
long. In single story homes with two separate
sleeping areas, a minimum of two smoke alarms is
required, one outside each sleeping area. In
multilevel or split level homes, as a minimum a
smoke alarm should be installed on the ground floor
between the staircase and any rooms in which a fire
might start and on each story in circulation areas
which form part of escape route (normally hallways
and landings).
3.2 Additional alarms should be installed in bedrooms in
anticipation of fires originating there, caused by
faulty wiring, lights, appliances, smokers or other
hazards.
3.3 For best protection, smoke alarms should be
installed in every room in your home, apart from
those listed in the Section 4 LOCATIONS TO
AVOID. Heat alarms should be used in kitchens,
boiler rooms, laundry rooms, garages and such like,
where smoke alarms would be unsuitable.
3.4 Install smoke alarms in circulation areas at a
distance no greater than 7.5m from the farthest wall,
no greater than 7.5m from a door to any room in
which a fire might start and no greater than 7.5m
from the next smoke alarm.
5.1 Remove the smoke alarm from the packaging and
detach the mounting plate
5.3 Drill the holes at the marks with a 3/16-inch (5mm)
drill.
5.4 Insert the anchor plugs and screw the mounting
bracket to the chosen position. DO NOT
OVER-TIGHTEN THE SCREWS, this will distort the
mounting bracket.
01
02 04 06 08
03 05 07
2. IMPORTANT SAFETY INFORMATION
3. WHERE TO LOCATE
5. HOW TO INSTALL
CONTENTS
WARNING!
PLEASE READ AND SAVE THESE INSTRUCTIONS.
PACKING LIST
Photoelectric alarms are generally more effective at
detecting slow, smoldering fires that smolder for hours
before bursting into flame. Sources of these fires may include
cigarettes burning in couches or bedding.
Ionization alarms are generally more effective at detecting
fast, flaming fires that consume combustible materials
rapidly and spread quickly. Sources of these fires may include
flammable liquids or paper burning in a waste container.
However, both types of alarms provide adequate detection of both
types of fires.
If you desire the earliest detection of both smoldering fires and
fast flaming fires, you should install smoke alarms that combine
both photoelectric and ionization sensing technologies in one unit.
PART NAME
QUANTITY
Smoke alarm
Smoke alarm
Mounting bracket
Mounting bracket
Anchor plug
Anchor plug
Screw
Screw
Manual
Manual
1 Piece
1 Piece
2 Pieces
2 Pieces
1 Piece
Battery Operated
9v replaceable battery included with this alarm.
Operating Light (LED)
Flashes approximately every 45 seconds confirming
unit is powered.
Low Battery Warning
Alarm beeps every 45 seconds when the battery
needs replacing.
Alarm Pause (Hush mode)
Silence your smoke alarm by momentarily pressing
the test button when non-emergency smoke (e.g.
steam), causes nuisance alarms. The red light
flashes every 10 seconds to remi
nd you that the
smoke alarm has been silenced. The alarm will
automatically reset after 10 minutes.
Sensitivity Test Button
Test the sensitivity, circuitry, batteries, horn.
Loud 85 Decibel Piezo Electric Alarm
Automatically resets when hazardous condition has
passed.
Easy Installation
Fixings supplied.
3.7 Read Section 4 LOCATIONS TO AVOID and
Section 13 LIMITATIONS OF SMOKE ALARMS in
this manual.
CAUTION: Research indicates that substantial
increases in warning time can be obtained with each
properly installed, additional alarm. It is strongly
recommended that advice in 3.3 above be followed to
ensure maximum protection.
Single Story,
one sleeping area
Single Story,
more than one sleeping areas
Smoke alarms for limited protection
Additional smoke alarms for better coverage
Heat alarms
KITCHEN
LIVING ROOM
TV ROOM
DINING
ROOM
BEDROOM
BEDROOM
BEDROOM
KITCHEN
LIVING ROOM
DINING ROOM
BEDROOM BEDROOM
BEDROOM
KITCHEN
FINISHED BASEMENT
LIVING ROOM
BEDROOMBEDROOM
HALL
Two Story dwelling
IMPORTANT
These alarms are intended to primarily for
single-occupancy private dwellings. For use in other
applications, the manufacturer's advice must be sought.
4. LOCATIONS TO AVOID
DO NOT locate smoke alarms:
4.1 In turbulent air from fans, heaters, doors, windows,
etc., which could draw smoke away from the alarm.
4.2 In high humidity area such as bathrooms and
shower rooms, or where the temperature exceeds
39˚C (100˚F) or falls below 5˚C (40˚F), as high
humidity can trigger nuisance alarm.
4.3 At the peak of an A frame ceiling. Dead air at the
top may prevent smoke from reaching the alarm in
time to provide early warning.
4.4 Less than 300mm (12 inches) from the wall when
mounted on the ceiling.
4.5 In insect-infested areas. Tiny insects may affect
performance.
4.6 In kitchens, boiler rooms, laundry rooms, garages.
Combustion particles from cooking or car exhaust
and dust and moisture could trigger a nuisance
alarm.
4.7 In very dusty or dirty areas. Dirt and dust can build
up and impair performance.
4.8 Within 300mm (12 inches) of light fittings or room
corners.
4.9 In locations which would make routine testing or
maintenance hazardous (e.g. over a stairwell).
4.10 On poorly insulated walls or ceilings.
4.11 Near objects such as ceiling decorations which
might impede the path of smoke to the alarm.
4.12 Within 1.5m (5 feet) of fluorescent light fittings.
Dead air area
Center
15cm
15cm
Model: CRG-100
9v Battery Operated
Photoelectric Smoke Alarm
Standards tested to: EN14604:2005/AC:2008
Warning! Test unit before installation and when installation is completed.
Screw
slots
Mounting plate
Mounting Hooks
5.2 Locate the mounting bracket in your chosen
position. Align the two longest mounting slots with
the line. Draw a mark in the center of each slot.
3.5 As it is impossible to predict the source of a fire, the
best location for an alarm is usually the center of a
room or hallway. If it is necessary to place a smoke
alarm on a wall, always locate the detection
element of the alarm 150mm to 300mm (6 to 12
inches) below the ceiling and the bottom of the
alarm above the level of doors and other openings.
3.6 In rooms with simple sloped, peaked or gabled
ceilings, install smoke alarms on the ceiling 900mm
(3 feet) from the highest point of the ceiling. Dead
air at the peak of a ceiling may prevent the smoke
from reaching the alarm in time to provide an early
warning.
DO NOT remove or disconnect battery to quiet
unwanted alarms.This will remove your protection.
Open windows or fan the air around smoke alarm to
silence it.
The test button accurately tests all smoke alarm
functions. DO NOT use any other test method. Test
smoke alarm weekly to ensure proper operation.
Observe and follow all local and national electrical and
building codes for in
stallation.
This smoke alarm IS NOTdesigned to be the
PRIMARY protection for buildings that require
complete fire alarm systems. Buildings of this type
include hotels, motels, dormitories, hospitals, nursing
homes, and group homes. This is true even if they
were once single family homes. However, this smoke
alarm MAY be used inside individual rooms as
SUPPLEMENTAL protection.
Install a smoke alarm in every room and on every level
of the home. Smoke may not reach the smoke alarm
for many reasons. For example, if a fire starts in a
remote part of the home, on another level, in a
chimney, wall, roof, or on the other side of a closed
door, smoke may not reach the smoke alarm in time to
alert household members. A smoke alarm will not
promptly detect a fire EXCEPT in the area or room in
which i
t is installed.
Smoke alarms may not alert every household
member every time. The alarm horn is loud in order
to alert individuals to a potential danger. However,
there may be limiting circumstances where a
household member may not hear the alarm (i.e.,
outdoor or indoor noise, sound sleepers, drug or
alcohol usage, the hard of hearing, etc.). If you
suspect that this smoke alarm may not alert a
household member, install and maintain specialty
smoke alarms. Household members must hear the
alarm's warning sound and quickly respond to it to
reduce the risk of damage, injury, or death that may
result from fire. If a household member is hard of
hearing, install special smoke alarms with lights or
vibrating devices to alert occupants.
Smoke alarms can sound their alarms only when they
detect smoke. Smoke alarms detect combustion
particles in the air. They do not sense heat, flame, or
gas. This smoke alarm is designed to give audible
warning of a developing fire. However, many fires are
fast-burning, explosive, or intentional. Others are
caused by carelessness or safety hazards. Smoke
may not reach the smoke alarm QUICKLY ENOUGH
to ensure safe escape.
Smoke alarms have limitations. This smoke alarm is
not foolproof and is not warranted to protect lives or
property from fire. Smoke alarms are not a substitute
for insurance. Homeowners and renters should insure
their lives and property. In addition, it is possible for
the smoke alarm to fail at any time. For this reason,
you must test the smoke alarm weekly and replace
every 10 years.
TEST
/
HUSH
TEST
/
HUSH
6/2018


Produkt Specifikationer

Mærke: CodeRED
Kategori: Røgalarm
Model: CRG-100

Har du brug for hjælp?

Hvis du har brug for hjælp til CodeRED CRG-100 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Røgalarm CodeRED Manualer

Røgalarm Manualer

Nyeste Røgalarm Manualer

Alecto

Alecto SD530 Manual

10 November 2025
SAVS

SAVS SA5MA Manual

8 November 2025
Alecto

Alecto SD110 Manual

4 November 2025
Kidde

Kidde 30CUA10-VCA Manual

2 November 2025
Alecto

Alecto BPB21 Manual

1 November 2025
Alecto

Alecto SD1010 Manual

1 November 2025
SAVS

SAVS SA5MB Manual

31 Oktober 2025
First Alert

First Alert CO615 Manual

23 Oktober 2025
X-Sense

X-Sense SD11 Manual

9 Oktober 2025