Læs gratis den danske manual til Panduit VS-CKP4-000 (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 4 personer og har en gennemsnitlig bedømmelse på 4.3 stjerner ud af 2.5 anmeldelser. Har du et spørgsmål om Panduit VS-CKP4-000, eller vil du spørge andre brugere om produktet?

Side 1/4
VeriSafe Insulation-Piercing
Connect Kit ion s
Insulation-Piercing Connectors for
VeriSafe AVT Sensor Lead Tapping on Copper Conductors
T-PMPI-322EN
Rev. 03 [12-2019]
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
Connection Kit Contents: contains connectors and ferrules for installation of VeriSafe AVT
Panduit VSC Series
Insulation-Piercing
Connectors
+
Panduit
F80-12
Ferrules
CONNECTION
KIT CATALOG
PART NUMBER
“RUN” Wire
(CODE WIRE)
“TAP” Wire AWG
(Terminated w/ Ferrule)
CONNECTOR
FERRULE
MIN. AWG
[METRIC, mm2]
MAX. G AW
[METRIC, mm2]
Catalog
P/N
Quantity
Catalog
P/N
Quantity
VS-CKP14-6
14 AWG
[2.1, r]
6 AWG
[13.3, r]
14 AWG STR
Class K
(Terminated w/ Ferrule)
VSC6
3
F80- 12
12
VS-CKP4- 000
4 AWG
[21.2, r]
3/0 AWG STR
[85, r]
VSC3/0
3
F80- 12
12
IMPORTANT:
M install Ferrules Tap Wires fore terminating Tap Wires into Panduit Connector. ust on be VSC
Terminate Tap Wires into Panduit VSC Connector before installing Connector on a Phase Wire.
Read Page 2; contains Safety Information and operating limits for Connector per product listing.
TO REDUCE THE RISK OF INJURY, USER
MUST READ INSTALLATION INSTRUCTIONS
BEFORE ATTEMPTING TO INSTALL
NOTE: In the interest of higher quality and value, Panduit products are
continually being improved and updated. Consequently, pictures
may vary from the enclosed product.
NOTE: Updates to this Installation Instructions may be available. Check
www.panduit.com for the latest version of this manual.
Email:
techsupport@panduit.com
EU Website:
www.panduit.com/emea
EU Email:
emeatoolservicecenter
@panduit.com
www.panduit.com
Panduit Corp.
USA Technical Support
Tel: 800-777-3300
Panduit Europe • EMEA Service Center
Tel: +31 546 580 452 • Fax: +31 546 580 441
© Panduit Corp. 20 18
INSTALLATION INSTRUCTIONS
Models: VS-CKP14-6, VS-CKP4-000
T-PMPI-322EN
Rev. 03 [12-2019]
DOC# T-PMPI-322EN Page Rev 03 [12-2019]: 2of 4
Safety Information
This installation instructions contains information and warnings which must be followed to ensure safe
termination and operation of the Insulation-piercing Connectors and an AVT Device.
Always de-energize panel and verify absence of voltage in the panel before attempting to install
connector. Do not install connector on an energized conductor.
Installer must also follow all AVT safety, installation, commissioning and operating steps from
the AVT Device Manual.
Connector is intended for one-time installation and use. Do not reuse nor re-install connector.
Connector Ratings Information
(1) Panduit VSC Series
Insulation-Piercing
Connectors are intended for
simplifying installation and
connection of PANDUIT
VeriSafe AVT Absence of
Voltage Testers to phase
(run) conductors.
(2) Panduit VSC Series
Insulation-Piercing
Connectors must be used
within the rated ating oper
environment and installed
according to the Listed
product ratings in this Table
Panduit CATALOG P/N (VSC Connector)
VSC6
VSC3/0
MAX. Operating Temperature (° C)
90°C
MAX. Operating Voltage (Volts)
600V
RUN
WIRE
Torque-driver SAE Hex Size
(Main Fastener)
5 /16”
3/8”
Installation Torque (Required)
40 in- lb
[4.52 N m]
80 in- lb
[9.04 N m]
Minimum Rated Wire Size, AWG
[Metric, mm2, rigid]
14 SOL
14 STR
[2.1, r]
4 SOL
4 STR
[21.2, r]
Maximum Rated Wire Size, AWG
[Metric, mm2, rigid]
6 SOL
6 STR
[ , r] 13.3
3/0 STR
[85, r]
TAP
WIRE
Torque-driver Installation Bit Size
T10 Torx
Torque-driver Installation Tool
( ) recommended
Wiha P/N 28502
Installation Torque (Required)
7 in- lb
[0.79 N m]
Listed
Tap Wire Ferrule and
Combinations
[Tap Wire Size/Type
a nd
Panduit Ferrule P/N]
#1
TAP Wire
14 AWG STR Class K
F80- 12 ferrule
Ferrule
#2
TAP Wire
16 AWG STR Class K
F - ferrule 78 12
Ferrule
#3
TAP Wire
18 AWG STR Class K
F76- ferrule 12
Ferrule
Recommended Crimp Tool (Panduit P/N)
CT- 1160
Overview of Installation Process (Connector)
Before proceeding fer to the simplied ow-chart below, which indicates the steps taken for each , re
connector ring installation Understand these steps before proceeding further with illustrated details. du .
WIRE
CONNECTOR
587H
Plan AVT
Sensor Lead
Routing and
Trim Length of
Sensor Leads
Strip insulation
on Sensor Leads
to proper length
for each Ferrule
Crimp
Ferrules
on he t
Sensor
Leads
Fully-insert crimped
wires into Connector
and tighten terminal
screw to specied
torque (tap wire)
Position Connector
onto Phase Wire
and tighten the
Main Fastener to
specied torque
0
1
2
3
11
12
13


Produkt Specifikationer

Mærke: Panduit
Kategori: Ikke kategoriseret
Model: VS-CKP4-000

Har du brug for hjælp?

Hvis du har brug for hjælp til Panduit VS-CKP4-000 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Panduit Manualer

Panduit

Panduit MEHT187 Manual

29 December 2024
Panduit

Panduit DIRBB2007S21W Manual

29 December 2024
Panduit

Panduit CDE3 Manual

29 December 2024
Panduit

Panduit EC001 Manual

29 December 2024
Panduit

Panduit PZICE Manual

15 December 2024
Panduit

Panduit PZICEA Manual

15 December 2024
Panduit

Panduit PZNDVK Manual

15 December 2024
Panduit

Panduit DIRLC9606RB1 Manual

11 December 2024
Panduit

Panduit EA001 Manual

9 December 2024

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer