Salus HTR230 Manual

Salus Termostat HTR230

Læs nedenfor 📖 manual på dansk for Salus HTR230 (3 sider) i kategorien Termostat. Denne guide var nyttig for 57 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/3
Dial Thermostat
Model: HTR230
INSTALLER MANUAL
SALUS Controls plc
SALUS House
Dodworth Business Park South,
Whinby Road,
Dodworth, Barnsley S75 3SP, UK.
Sales: T: +44 (0) 1226 323961
E: sales@salus-tech.com
Technical: T: +44 (0) 1226 323961
E: tech@salus-tech.com
www.salus-controls.com
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc reserve the right to
change specification, design and materials of products listed in this brochure without prior notice.
Issue Date: Dec 2015
00190
For PDF Installation guide please
go to www.salus-manuals.com
8. Technical Specification
Model: HTR230
Voltage: 230 V AC, +-10%, 50/60 Hz
Operating Performance: 230 V: 1,8 W
Temperature setback:
Temperature range:
2°C-4°C
5°C- 30°C
Span: +/- 0,5°C
Calibration:Yes, with jumper
Storage temperature: -20°C to +60°C
Ambient temperature: 0 °C up to 45 °C
Degree of protection:IP 30
CE conformity according to: Class II ( EN60730 )
Housing material:PC, V2
Color: RAL 9010 pure white
Connection: Screw terminal
Weight 90g net / 135g gross
Puls-wide-modulation:
(PWM) Yes
Valve protection:
Heating and Cooling:
Cooling blocked:
Dimensions:
Yes
Yes, automatically Change Over on the CO terminal
Yes, with jumper
85mm*85mm*25mm
Warranty
SALUS Controls warrants that this product (HTR230) will be free from any
defect in materials or workmanship, and shall perform in accordance with
its specification, for a period of five years from the date of installation.
SALUS Controls sole liability for breach of this warranty will be (at its option) to repair
or replace the defective product.
Customer Name: ......................................................................................................................................................
Customer Address: .................................................................................................................................................
............................................................................................................................................................................................
....................................................................................... Post Code: ...........................................................................
Tel No: .................................................................... Email: .......................................................................................
Engineers Company: ..........................................................................................................................................
Tel No: ...................................................................... Email: ....................................................................................
Instalation Date: ....................................................................................................................................................
Engineers Name: ...................................................................................................................................................
Engineers Signature: ...........................................................................................................................................
6. Protection Function
7. Control Patterns
5. Thermostat Functions
NSB (Night SetBack) Function
NSB Mode depends on the NSB wired connection.
0V = NSB OFF
230V= NSB ON
The NSB signal is activated every 1 second. When the signal is received the
setpoint temperature will be set at 2°C or 4°C.± ±
Heating and Cooling Selection
The Heating/Cooling function is determined by the CO terminal connection.
CO 0V = Heat mode
CO 230V= Cool mode
Cooling Blocked function
Cooling Enabled:
Set the jumper on ON . The thermostat will run in normal cooling mode.
That means that it will open/close the actuators when necessary. The LED will be
BLUE when the cooling function is running.
Cooling Disabled:
Set the jumper on OFF . The actuator will be closed and the LED will
be off.
Heat cut o at high/low temperature:
When room temperature is over 36°C or under 4°C, all heating/cooling outputs
will be turned off.
Short cycle protection:
When Cooling Mode is enabled the minimum interval between Relay ON/OFF
is 3 minutes.
Valve Protection:
Set the jumper on ‘ON’ to disable the function or on ‘OFF to enable it. Turn on the
valve for 5 minutes every week to prevent any damage to the valve.
Sensor Malfunction:
If the temperature sensor or temperature sensor compensation is open the LED
will flash BLUE/RED alternatively.
If CO terminal is connected and the Heating Mode is ON, the PWM function
will be activated.
If CO terminal is disconnected and the Cooling Mode is ON the ON/OFF control
output will be activated.


Produkt Specifikationer

Mærke: Salus
Kategori: Termostat
Model: HTR230

Har du brug for hjælp?

Hvis du har brug for hjælp til Salus HTR230 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Termostat Salus Manualer

Salus

Salus RT510RF+ Manual

12 Maj 2024
Salus

Salus WT100 Manual

24 Marts 2024
Salus

Salus RT310ISR Manual

13 Marts 2024
Salus

Salus RT310RF Manual

30 Januar 2024
Salus

Salus RT510TX+ Manual

23 Januar 2024
Salus

Salus EP101 Manual

20 September 2023
Salus

Salus RT510LG5V+ Manual

19 September 2023
Salus

Salus ST620 Manual

13 September 2023
Salus

Salus ERT 50 Manual

25 August 2023

Termostat Manualer

Nyeste Termostat Manualer