Carrier AquaForce 30XW Manual

Carrier Klimaanlæg AquaForce 30XW

Læs gratis den danske manual til Carrier AquaForce 30XW (48 sider) i kategorien Klimaanlæg. Denne vejledning er vurderet som hjælpsom af 2 personer og har en gennemsnitlig bedømmelse på 4.6 stjerner ud af 1.5 anmeldelser. Har du et spørgsmål om Carrier AquaForce 30XW, eller vil du spørge andre brugere om produktet?

Side 1/48
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300144-01 Printed in U.S.A. Form 30XW-9SI Rev. A Pg 1 5-21 Replaces: 30XW-8SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . .1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
SYSTEM PIPING
MINIMUM LOOP VOLUME
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . .2
Step 2 — Prepare Installation Site . . . . . . . . . . . . . . . .2
Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . .24
Step 4 — Connect Piping . . . . . . . . . . . . . . . . . . . . . . . .25
EVAPORATOR FLUID, CONDENSER FLUID, VENT,
AND DRAIN PIPING
CONDENSER FLUID CONTROL VALVE
INSTALL PRESSURE RELIEF REFRIGERANT VENT
PIPING
FILL FLUID LOOP
WATER TREATMENT
BRINE UNITS
PREPARATION FOR YEAR-ROUND OPERATION
DUAL CHILLER CONTROL
Step 5 — Make Electrical Connections. . . . . . . . . . .33
FIELD POWER CONNECTIONS
FIELD CONTROL POWER CONNECTIONS
EVAPORATOR PUMP CONTROL
CONDENSER PUMP CONTROL
CARRIER COMFORT NETWORK
®
COMMUNICATION
BUS WIRING
BACNET COMMUNICATION OPTION WIRING
NON-CCN COMMUNICATION WIRING
FIELD CONTROL OPTION WIRING
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . .43
ENERGY MANAGEMENT MODULE
REMOTE ENHANCED DISPLAY (OR TOUCH PILOT
DISPLAY)
CONTROL ACCESSORIES
MISCELLANEOUS ACCESSORIES
Step 7 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . .43
Step 8 — Charge Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Step 9 — Install Field Insulation and Lagging . . . .44
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the litera-
ture, tags and labels attached to the unit, and other safety precau-
tions that may apply.
Follow all safety codes, including ANSI (American National Stan-
dards Institute) Z223.1. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
0
WARNING
Before performing service or maintenance operations on unit,
turn off main power switch to unit. Electrical shock could
cause personal injury.
WARNING
Improper installation, adjustment, alteration, service, or main-
tenance can cause injury or property damage. Refer to this
manual. For assistance or additional information, consult a
qualified installer, service agency, or the gas supplier.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gage for how
much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes and
regulations. DO NOT leave refrigerant system open to air any
longer than the actual time required to service the equipment.
Seal circuits being serviced and charge with dry nitrogen to
prevent oil contamination when timely repairs cannot be com-
pleted. Failure to follow these procedures may result in dam-
age to equipment.
AquaForce
®
30XW150-400
Water-Cooled Liquid Chillers
2
INTRODUCTION
These instructions cover installation of 30XW liquid chillers with
electronic controls and units with factory-installed options
(FIOPs).
System Design
SYSTEM PIPING
Proper system design and installation procedures should be fol-
lowed closely. The system must be constructed with pressure tight
components and thoroughly tested for installation leaks.
Installation of water systems should follow sound engineering
practice as well as applicable local and industry standards. Im-
properly designed or installed systems may cause unsatisfactory
operation and/or system failure. Consult a water treatment special-
ist or appropriate literature for information regarding filtration,
water treatment, and control devices.
MINIMUM LOOP VOLUME
The preferred minimum loop volume is dependent on the type of
application. In order to obtain leaving water temperature stability
for comfort cooling applications, a minimum of 3 gallons per ton
(3.25 liters per kW) is required on all unit sizes. For process cool-
ing applications or applications where high stability is critical, the
loop volume should be increased to 6 to 10 gallons per ton (6.46 to
10.76 liters per kW) of cooling. In order to achieve this volume, it
may be necessary to add a water storage tank to the water loop. If
a storage tank is added to the system, it should be installed on the
return/entering fluid side and properly vented so that the tank can
be completely filled and all air eliminated. Failure to do so could
cause lack of pump stability and poor system operation. Any stor-
age tank that is placed in the water loop should have internal baf-
fles to allow thorough mixing of the fluid. See Fig. 1.
Fig. 1 — Tank Baffling
INSTALLATION
Step 1 — Inspect Shipment
Inspect unit for damage upon arrival. If damage is found, immedi-
ately file a claim with the shipping company. Verify proper unit
delivery by checking unit nameplate data and the model number
nomenclature shown in Fig. 2. Do not store units in an area ex-
posed to weather because of sensitive control mechanisms and
electronic devices. Chiller should be stored indoors, protected
from construction dirt and moisture and with temperatures be-
tween 40°F (4.4°C) and 120°F (48.C) and relative humidity be-
tween 10% and 80% (non-condensing).
Step 2 — Prepare Installation Site
Locate unit indoors. When considering unit location, consult Na-
tional Electrical Code (NEC, U.S.A.) and local code requirements.
Allow sufficient space for wiring, piping, and service. Install unit
in an area which will not be exposed to ambient temperatures be-
low 50°F (10°C).
Be sure surface beneath unit is level and is capable of supporting
the operating weight of the unit. See Tables 1 and 2 and Fig. 3-7
for unit mounting and operating weights and dimensions.
If necessary, add supporting structure (steel beams or reinforced
concrete slabs) to floor to transfer weight to nearest beams. See
Fig. 3-5 for clearance details.
Allow the following clearances for service access:
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Rear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ft (610 mm)
Ends . . . . . . . . . . . . . . . . . . . . . . . . tube length at one (either) end;
. . 3 ft (914 mm) at opposite end.
CAUTION
This unit uses a microprocessor control system. Do not short
or jumper between terminations on circuit boards or modules;
control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module con-
nections. Always touch a chassis (grounded) part to dissipate
body electrostatic charge before working inside control center.
Use extreme care when handling tools near boards and when
connecting or disconnecting terminal plugs. Circuit boards can
easily be damaged. Always hold boards by the edges and
avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy.
If not installed and used in accordance with the instruction
manual, it may cause interference to radio communications. It
has been tested and found to comply with the limits for a Class
A computing device pursuant to International Standard in
North America EN 61000-2/3 which are designed to provide
reasonable protection against such interference when operated
in a commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which case
the user, at his own expense, will be required to take whatever
measures may be required to correct the interference.
Always store and transport replacement or defective boards in
anti-static shipping bag.
BAD
BAD
GOOD
GOOD


Produkt Specifikationer

Mærke: Carrier
Kategori: Klimaanlæg
Model: AquaForce 30XW

Har du brug for hjælp?

Hvis du har brug for hjælp til Carrier AquaForce 30XW stil et spørgsmål nedenfor, og andre brugere vil svare dig