Schneider MTN647395 Manual


Læs nedenfor 📖 manual på dansk for Schneider MTN647395 (2 sider) i kategorien Ikke kategoriseret. Denne guide var nyttig for 26 personer og blev bedømt med 4.5 stjerner i gennemsnit af 2 brugere

Side 1/2
V6473-562-04 11/21
Switch actuator REG-K/x230/16 with manual mode and current detection© Merten2009V6473-562-0411/21
SpaceLogic KNX
Switch actuator REG-K/x230/16 with
manual mode and current detection
Operating instructions
SpaceLogic KNX
Switch actuator REG-K/2x230/16 with
manual mode and current detection
Art. no. MTN647395
SpaceLogic KNX
Switch actuator REG-K/8x230/16 with
manual mode and current detection
Art. no. MTN647895
SpaceLogic KNX
Switch actuator REG-K/12x230/16
with manual mode and current
detection
Art. no. MTN648495
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
Connecting to installation networks
Connecting several electrical devices
Laying electric cables
Connecting and establishing KNX networks
Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
The output may carry electrical current even when the
load is switched off.
When working on the device: Always disconnect the
device from the supply by means of the fuse in the in-
coming circuit.
Even if the manual switch is in the „OFF“ position, a
KNX telegram can switch the connections to being
live at any time. Before working on the device, always
diconnect the fuse in the incoming circuit from the
supply.
Failure to follow these instructions will result in
death or serious injury.
en
L 2L 1
5 6 7 81 2 3 4
LL 1 2 LL 3 4 LL 5 6 LL 7 8
567891011121234
LL 5 6 LL 7 8 LL 9 10 LL 11 12LL 1 2 LL 3 4
L 2L 1
5 6 7 81 2 3 4
LL 1 2 LL 3 4 LL 5 6 LL 7 8
567891011121234
LL 5 6 LL 7 8 LL 9 10 LL 11 12LL 1 2 LL 3 4
The switch actuator REG-K/x230/16 with manual mode
and current detection (referred to below as the actuator)
can switch
two loads (MTN647395) or
eight loads (MTN647895) or
twelve loads (MTN648495)
via separate, floating make contacts.
You can also manually switch the connected loads with
manual switches on the actuator without bus voltage.
The actuator has a bus coupler. It is installed on a DIN rail
TH 35 according to EN 60715, with the bus connection
made via a bus connecting terminal. It is supplied with
power from the bus voltage. A data rail is not required.
The actuator also has integrated current detection wich
measures the load current of each channel.
ABus connection terminal, max. 4 core pairs
BProgramming LED (red)
CProgramming button
DCable cover
EOperating LED „RUN“ (green)
FManual switch
GScrew terminals
The device may be damaged!
Always operate the product in compliance with the
specified technical data.
Do not use the current detection function for applica-
tions relevant to safety.
Connect only pure ohmic loads to a channel with di-
rect current (DC).
Only install devices with at least basic insulation next
to the device.
Failure to follow these instruction can result in
equipment damage.
Getting to know the actuator
Connections, displays and operating
elements
L L 2L L 1
KNX
1 2
D
C
AB
E
F
G
½CAUTION
Strong magnetic fields can influence the current
measurement. Install devices with a strong mag-
netic field (e.g. wound transformers such as bell
transformers) at least 2 cm away from the actua-
tor.
1Set the actuator onto the DIN rail.
2Connect KNX.
¼WARNING
Risk of death from electric shock. The device
can become damaged.
Safety clearance must be guaranteed in accord-
ance with IEC 60664--1. There must be at least 4
mm between the individual cores of the 230 V
supply cable and the KNX line A.
Mounting the actuator
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
Voltage may be present at the outputs when the mains
voltage is connected to the system.
If subjected to strong vibrations during transportation,
the switch contacts might change to the enabled state.
After connecting the bus voltage, set the relays of the
channels to the position desired simply by switching
„On/Off“ or by changing the manual switch to „OFF“.
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
Protect the switch contacts with a series-connected
16 A circuit breaker.
Failure to follow these instruction can result in
equipment damage.
1
2
1 2
3 4
5 mm
230 V
4 mm
A