Schneider TeSys D LR97D25 Manual

Schneider Ikke kategoriseret TeSys D LR97D25

Læs gratis den danske manual til Schneider TeSys D LR97D25 (4 sider) i kategorien Ikke kategoriseret. Denne vejledning er vurderet som hjælpsom af 2 personer og har en gennemsnitlig bedømmelse på 4.4 stjerner ud af 1.5 anmeldelser. Har du et spørgsmål om Schneider TeSys D LR97D25, eller vil du spørge andre brugere om produktet?

Side 1/4
W9 1636662 01 A03
02 - 2011
1/4
www.schneider-electric.com
A
B
DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Disconnect all power before servicing
equipment.
Failure to follow these instructions
will result in death or serious injury.
LR97Dppp
0.3 - 1.5 A
1.2 - 7 A
5 - 25 A
20 - 38 A
Relay setting range
LR97D015
LR97D07
LR97D25
LR97D38
Type
Power
supply
(1) Select function by dip switch:
b dip switch 1: 1 phase / 3 phase
b dip switch 2: Manual / Auto reset
Available for 3 phase utilisation only (Dip SW on "3P" position)
Combined signals from red and green LEDs indicate
motor status including trip causes.
Condition
LED Signal (Pulse Chart)
Green LED
On
On
On
Off
Off
Off
Off
Off
Off
Off
On
Red LED
Power on
Starting
Steady state
Overloading
Overcurrent
Trip
Locked rotor
Phase
Loss
L1
L2
L3
2T1 4T2 6T3
A1 A2 98 NO NC95 96
Test/Stop
Reset
Relay output
Green LED
(LED OK)
Load
O-Time
D-Time
Red LED
(LED OL)
PLEASE NOTE:
b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
b No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
website at www.schneider-electric.com.
Operating and Function
b LR97D, solid state overload relay, compares motor
current with preset load current threshold (LOAD).
b Three phase motor currents are monitored through
three internal current transformers.
b D-Time counts down and is only available for
motor starting.
During steady state, if motor current is greater than the current setting (overloaded), LR97D
switches its contacts after O-Time.
In case of phase failure and locked rotor, trip delay time is 3 s and 0.5 s respectively.
b For shear-pin (mechanical shock) protection, set O-Time knob to its minimum in order to trip in 0.2-0.3 s.


Produkt Specifikationer

Mærke: Schneider
Kategori: Ikke kategoriseret
Model: TeSys D LR97D25
Kode for international beskyttelse (IP): IP20
Bredde: 45 mm
Dybde: 67.5 mm
Højde: 67.5 mm
Vægt: 172 g
Pakkevægt: 182 g
Pakkedybde: 69 mm
Pakkebredde: 76 mm
Pakkehøjde: 50 mm
Opbevaringstemperatur (T-T): -30 - 80 °C
Driftstemperatur (T-T): -25 - 60 °C
Indgangsfrekvens: 50/60 Hz
Nominel indgangsspænding: 600 V
Garantiperiode: 1.5 År
Nominel impulsmodstandsspænding (Uimp): 6 kV
Nominel isolationsspænding: 600 V

Har du brug for hjælp?

Hvis du har brug for hjælp til Schneider TeSys D LR97D25 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Schneider Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer

MuxLab

MuxLab 500439 Manual

5 November 2025
GVM

GVM BL160-II Manual

5 November 2025
Rockville

Rockville SS6 Manual

5 November 2025
MEPROLIGHT

MEPROLIGHT MCO PRO Manual

5 November 2025
XPG

XPG Battlecruiser II Manual

5 November 2025
Hosa

Hosa USQ-110 Manual

5 November 2025