GB
¼
DANGER
Risk of fatal injury from electrical current.
All work on the device should only be carried out
by trained and skilled electricians. Observe the
country-specific regulations as well as the valid
KNX guidelines.
½CAUTION
The device could be damaged.
- Only operate the device according to the
specifications stated in the Technical data.
- All devices that are installed next to the actuator
must be equipped with at least basic insulation.
The switch actuator REG-K/2x230/10 with manual mode
(referred to below as the actuator) can switch two
loads via separate, floating make contacts.
You can switch the actuator to manual operation and
check that it works even without ETS programming, and
you can control the connected loads directly at the
actuator in the event of a bus failure.
The actuator has a bus coupler. It is installed on a DIN
rail, with the bus connection made via a bus connecting
terminal. It is supplied with power from the bus voltage.
A data rail is not required.
For your safety
Getting to know the switch actuator
AUnder the cable cover: Bus connecting terminal,
programming button and programming LED (red)
BOperating LED "RUN" (green)
CChannel status LEDs (yellow) for the corresponding
channel
DChannel keys for manual control of the
corresponding channel, only respond when manual
operation is switched on
EChannel terminals for load voltage
FManual operation key "Manual"
GManual operation LED "Manual" (red)
HFlap forward to open
1Set the actuator onto the DIN rail.
2Connect KNX.
¼
WARNING
Risk of fatal injury from electrical current. The
device could become damaged.
Safety clearance must be guaranteed in
accordance with IEC 60664-1. There must be at
least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
Connections, displays and operating
elements
Mounting the actuator
A
B
G
F
H
E
D
C
1
2
1 2
34
5 mm
230 V
4 mm
KNX
¼
DANGER
Risk of fatal injury from electrical current.
Voltage may be present at the outputs when the
mains voltage is connected to the system.
If subjected to strong vibrations during
transportation, the switch contacts might change
to the enabled state.
After connecting the bus voltage, wait 30
seconds. The relays of the channels will be
switched off. Set the relays of the channels to the
position desired simply by switching "On/Off".
3Connect the bus voltage.
4Wait at least 30 seconds.
5Set the relays of the channels to the position
desired simply by switching "On/Off".
½CAUTION
The actuator can be damaged. Protect:
- Connections with a 10-A circuit breaker
connected upstream. If you use separate fuses
for the connections of two related switching
channels, these must be on the same phase.
6Connect the load
7Connect the load voltage.
Now you can check the functionality of the actuator and
the connected loads without having to load the
application from the ETS. (See the "Operating the
actuator" section.)
1Press the programming button.
The programming LED lights up.
2Load the physical address and application into the
device from the ETS.
The programming LED goes out.
The operating LED lights up: The application was loaded
successfully, the device is ready for operation.
Putting the actuator into operation
KNX
L
L
N
10A
10A
10A
L L
1 2 1 2
Switch actuator REG-K/2x230/10 with
manual mode
Operating instructions
Art. no. MTN649202


Produkt Specifikationer

Mærke: Schneider
Kategori: Ikke kategoriseret
Model: MTN649202

Har du brug for hjælp?

Hvis du har brug for hjælp til Schneider MTN649202 stil et spørgsmål nedenfor, og andre brugere vil svare dig




Ikke kategoriseret Schneider Manualer

Ikke kategoriseret Manualer

Nyeste Ikke kategoriseret Manualer