Pro1 T731WO Manual

Pro1 Termostat T731WO

Læs gratis den danske manual til Pro1 T731WO (5 sider) i kategorien Termostat. Denne vejledning er vurderet som hjælpsom af 3 personer og har en gennemsnitlig bedømmelse på 3.7 stjerner ud af 2 anmeldelser. Har du et spørgsmål om Pro1 T731WO, eller vil du spørge andre brugere om produktet?

Side 1/5
T731W(O)
Installation Manual
Pro1 Technologies
Toll Free : 888-776-1427
Web: www.pro1iaq.com
Hours of Operation: M-F 9AM - 6PM Eastern
Thermostat Application Guide
Description
Gas or Oil Heat
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (With Electric Aux.)
Multi-Stage Systems
Heat Only Systems - Floor or Wall Furnace
Cool Only Systems
Millivolt
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Power Type
Battery Power
Hardwire (Common Wire)
Hardwire (Common Wire) with
Battery Backup
Table of Contents
Installation Tips
Thermostat Quick Reference
Base Module Mounting Tips
Wiring
Technician Setup
Establishing Communication
Network Specications
Specications
Page
A trained, experienced
technician must install this
product.
Carefully read these
instructions. You could damage
this product or cause a
hazardous condition if you fail
to follow these instructions.
Una version en español de este
manual se puede descargar en
la pagina web de la compañia.
Rev. 2132
Mount Thermostat
Align the 4 tabs on the subbase
with corresponding slots on the
back of the thermostat, then push
gently until the thermostat snaps
in place.
Battery Installation
Battery installation is
optional if thermostat is
hardwired (R and C terminal
connected to 24V power).
Important:
High quality alkaline batteries are recommended.
Rechargeable batteries or low quality batteries
do not guarantee a 1-year life span.
Insert 2 AA
Alkaline batteries
(included). High
quality alkaline
batteries are
recommended.
Installation Tips
2
2
2
2
4-5
8-11
12-16
1
1
1
1
2-3
Installation Tips Thermostat Quick Reference
Getting to know your thermostat
3
3
3
3
4
4
4
4
Subbase Installation
The thermostat should be installed approximately 4 to 5 feet above the
oor. Select an area with average temperature and good air circulation.
• Close to hot or cold air ducts
That are in direct sunlight
With an outside wall behind
the thermostat
• In areas that do not require
conditioning
Where there are dead spots
or drafts
(in corners or behind doors)
Where there might be
concealed chimneys or
pipes
Wall Locations
Vertical Mount
Horizontal Mount
For vertical mount put one screw on the top
and one screw on the bottom.
For horizontal mount put one screw on the
left and one screw on the right.
All of our products are mercury free.
However, if the product you are
replacing contains mercury, dispose of
it properly. Your local waste
management authority can give you
instructions on recycling and proper
disposal.
Pick an installation location that is easy for
the user to access. The temperature of the
location should be representative of the
building.
Installation Tip
Mercury Notice
Do not install
thermostat in locations:
Failure to disconnect the power before
beginning to install this product can
cause electrical shock or equipment
damage.
Installation Tip:
Electrical Hazard
U.S. Registered Trademark. Patents pending
Copyright 2020 All Rights Reserved.
Heat Pump (With Gas Aux.)
Emergency Heat
Conventional Single Stage Furnace
Geothermal
High, Medium and Low Fan Speed
No
No
Yes
Yes
19
Located on the back of thermostat.
P.O. Box 3377
Springeld, MO 65808-3377
Glow in the Dark Light Button
Setpoint Buttons
LCD
System Button
Fan Button
R
17-18
20
6-7
Occupancy Sensor
(Occupancy Model Only)
5
5
5
5
6
6
6
6
Base Module - PTAC Installation
Side Mount:
Inside PTAC
Housing
Front Mount:
Inside PTAC
Housing
Base Module Mounting Tips
Range between the thermostat and the base module is up to 100 feet
with no obstructions and up to 50 feet through standard building
materials. To optimize the range try placing the base module with no
metal between it and the thermostat.
The base module is designed to be mounted behind the front grille
of a packaged terminal air conditioner (PTAC). Refer to the PTAC
manufacturers manual for instruction to remove the front grille.
Check clearance to ensure the t of front grille after base module
installation. See below for a few location recommendations.
The low battery indicator is displayed when the AA battery power is low. If the user
fails to replace the battery within 21 days, the screen will only show the low battery
indicator but maintain all functionality. If the user fails to replace the batteries after
an additional 21 days (days 22-42 since rst “low battery display) the setpoints will
change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from
either of these, it will hold for 4 hours then return to either 55˚F or 85˚F. After day 63
the batteries must be replaced immediately to avoid freezing or overheating because
the thermostat will shut the unit o until the batteries are changed.
Important
Ambient Temperature:
Displays the current room temperature
Energy Ecient Globe:
Indicates you are making an energy ecient set at
temperature.
Staging Indicaators:
If these or the fan indicators are ashing, it means that the system is in a delay of some
type (compressor delay, cooling fan delay, or staging delay) or a pending change.
Set At Temperature:
Displays the selected desired room temperature.
Wireless Symbol: Indicates you have a wireless connection.
1
2
3
Next
Heat
Cool
Prev
Auto
On LHM
Set At
COOL ON
HEAT ON
FAN ON
STAGE 1+2
Next
Heat
Cool
Prev
Auto
On LHM
Set At
COOL ON
HEAT ON
FAN ON
STAGE 1+2
Thermostat Quick Reference
Low Battery Indicator: Replace batteries when this indicator
appears.
1
2
3
Base Module Mounting Tips
7
7
7
7
Wiring
8
8
8
8
When Working With A Vertical Unit
1. Do not mount Module inside the cabinet of the unit, or in a
metal enclosure.
2. Mount on the outside of the unit to maximize wireless
communication.
When Working With A Metal Sleeve Cabinet, Room Cabinet,
or PTAC Cover
1. If cabinet has open bottom, mount the module just inside the
cabinet as close to the open bottom as possible without placing it in
danger of being bumped or touched by furnishings, vaccum, etc.
2. Another good module location would be on the underside of the
top of the cabinet or cover. Directly behind the open Louver/Grill.
Front Panel
Chasis
Sleeve Cabinet
Rough-In
Wall Opening
Caution:
Electrical Hazard
All components of the
control system and the
thermostat installation must
conform to Class II circuits
per the NEC Code.
Warning:
Do not overtighten terminal
block screws, as this can
damage the terminal block.
A damaged terminal block
can keep the thermostat
from tting on the subbase
correctly or cause system
operation issues.
Installation Tip
Max Torque = 6in-lbs.
Wiring
If you are replacing a thermostat,
make note of the terminal
connections on the thermostat
that is being replaced. In some
cases the wiring connections will
not be color coded. For example,
the green wire may not be
connected to the G terminal.
Loosen the terminal block
screws. Insert wires then
retighten terminal block screws.
Place nonammable insulation
into wall opening to prevent
drafts.
1.
2.
3.
Terminal Designations
R
Failure to disconnect the power
before beginning to install this
product can cause electrical
shock or equipment damage.
C
B
O
GL
Heat Pump System
1 HEAT 1 COOL / 2 HEAT 1 COOL
Conventional System
1 HEAT 1 COOL
Transformer Power
Transformer Common
Changeover Valve
Energized in HEAT
Fan Relay, Low
Changeover Valve
Energized in COOL
Second Stage of HEAT
First Stage of HEAT and COOL
Transformer Power
Transformer Common
Fan Relay, Low
First Stage of HEAT
First Stage of COOL
N/A
N/A
GH
W
Y
Fan Relay, High Fan Relay, High


Produkt Specifikationer

Mærke: Pro1
Kategori: Termostat
Model: T731WO

Har du brug for hjælp?

Hvis du har brug for hjælp til Pro1 T731WO stil et spørgsmål nedenfor, og andre brugere vil svare dig




Termostat Pro1 Manualer

Pro1

Pro1 T721 Manual

20 August 2025
Pro1

Pro1 T731WO Manual

20 August 2025
Pro1

Pro1 R251S Manual

20 August 2025
Pro1

Pro1 T805 Manual

20 August 2025
Pro1

Pro1 T701i Manual

20 August 2025
Pro1

Pro1 T721i Manual

20 August 2025
Pro1

Pro1 E219 Manual

20 August 2025
Pro1

Pro1 T701 Manual

20 August 2025
Pro1

Pro1 T755S Manual

20 August 2025
Pro1

Pro1 T501M Manual

20 August 2025

Termostat Manualer

Nyeste Termostat Manualer